ONE-WAY FLOW ALTITUDE VALVE
with SOLENOID (On-Off) FEATURE

960-15
660-15

Installation Guidelines

• Prior to installation, flush line to remove debris.

• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid

installing valve 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.

• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact

control valve. Damage or improper valve seating may occur.

• Provide adequate clearance for valve servicing and maintenance.

• Install pressure gauges to monitor valve inlet, outlet, and static head pressure.

• Provide adequate drain for cover chamber discharge if “wet drain” option is selected. Consult “Valve

Cover Capacity” chart on appropriate main valve Engineering Bulletin.

Install static tank head sense line. For optimum control, sense line should be: 1) Installed with an

upward angle (towards reservoir) to avoid air accumulation, 2) Connected no further than forty-five pipe
diameters from the reservoir, and 3) A minimum of 1/2” diameter.

• Connect Solenoid Pilot to appropriate power source in compliance with local electrical codes.

Other AMES Altitude Control Valves

960 / 660

One Way Flow Altitude Valve

960-13 / 660-13

One Way Flow Altitude Valve with Delayed Opening Feature

960-15-17 / 660-15-17

Two Way Flow Altitude Valve with Solenoid Override Feature

960-17 / 660-17

Two Way Flow Altitude Valve

962 / 662

One Way Flow Altitude Valve with Pressure Sustaining Feature

Advertising