MODULATING FLOAT VALVE

979
679

Operation

The AMES Model 979 / 679 Modulating Float Control Valve is designed to automatically maintain a constant
liquid level in a tank or reservoir. It is controlled by a remote mounted Modulating Float Pilot designed to: 1)
Modulate Open (allowing fluid out of the main valve cover chamber) when reservoir level decreases, and,
2) Modulate Closed (allowing fluid to fill the main valve cover chamber) when reservoir level increases. A
decrease in reservoir level causes the valve to modulate towards an open position, allowing reservoir level
to increase. An increase in reservoir level causes the valve to modulate towards a closed position, allowing
reservoir level to decrease.

If desired, the modulating action of the valve can be “reversed” by inverting or “reversing” the action of
the Modulating Float Pilot. The Modulating Float Control is remotely mounted from the valve, and field
connected with 3/8” minimum copper tubing in accordance with factory piping schematic.

Installation Guidelines

• Prior to installation, flush line to remove debris.

• Install valve horizontally “in line” (cover facing up), so flow arrow matches flow through the line. Avoid

installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.

• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact

control valve. Damage or improper valve seating may occur.

• Provide adequate clearance for valve servicing and maintenance.

• Install pressure gauge to monitor valve inlet pressure.

• Connect Modulating Float Control to main valve using 3/8” diameter minimum copper tubing (field

installed) in accordance with factory piping schematic.

• Modulating Float Control should be mounted in a field installed “stilling well” for protection against surface

turbulence and interference.

Other AMES Float Control Valves

972 / 672

On-Off Float Control Valve (4” & smaller)

972-19 / 672-19

On-Off Float Control Valve (6” & larger)

972-20 / 672-20

On-Off Float Control Valve with Pressure Sustaining Feature

979-15 / 679-15

Modulating Float Control Valve with Solenoid (On-Off) Feature

979-20 / 679-20

Modulating Float Control Valve with Pressure Sustaining Feature

Advertising
This manual is related to the following products: