Ames Fire & Waterworks A200 Bronze Anti-Siphon Pressure Vacuum Breakers User Manual

Series a200, Installation, maintenance, & repair, Installation requirements

Advertising
background image

RP/IS-A-A200

A200

3

4

" (20mm)**

A200

3

4

" – 1" (20-25mm)** has tee handles

1

1

4

" – 2" (32 – 50mm)**

Installation, Maintenance, & Repair

Series A200

Pressure Vacuum Breakers

Sizes:

3

4

" – 2" (20 – 50mm)**

www.amesfirewater.com

A Division of Watts Water Technologies, Inc.

Testing

For field testing procedure, refer to Ames installation sheets

IS-A-ATG-1 found on

www.amesfirewater.com.

For other repair kits and service parts, refer to our Backflow

Prevention Products Repair Kits & Service Parts price list

PL-A-RP-BPD found on

www.amesfirewater.com.

For technical assistance, contact your local Ames representative.

1. Install 12" (300mm) above highest point of downstream piping.
2. Install bonnet side up and allow for accessibility for testing /service.
3. Install where discharge or spillage is not objectionable.
4. Do not undersize supply or oversize the valve in relation to demand.
5.

Protect from freezing.

6. ASSE Standard 1020 requires that the atmospheric vent valve

remains open until the valve body pressure exceeds 1lb. Until this

pressure is reached, some amount of spillage will occur at the at-

mospheric vent. In order to minimize this leakage on startup close

the downstream shutoff valve and open inlet valve quickly.

Installation Requirements

Outlet Drain Valve

Flow

Sprinkler System

Piping

12" (300mm) Minimum Clearance

Above the highest Point of

Downstream Piping.

Main Shutoff Valve

Upstream (Inlet) Drain

Valve Pit

Union

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can

result in death, serious personal injury, property damage, or

damage to the equipment.
Keep this Manual for future reference.

You are required to consult the local building and plumbing

codes prior to installation. If the information in this manual

is not consistent with local building or plumbing codes,

the local codes should be followed. Inquire with governing

authorities for additional local requirements.

WARNING

!

Need for Periodic Inspection/Maintenance: This product must

be tested periodically in compliance with local codes, but at least

once per year or more as service conditions warrant. If installed on

a fire suppression system, all mechanical checks, such as alarms

and backflow preventers, should be flow tested and inspected in

accordance with NFPA 13 and/or NFPA 25. All products must be

retested once maintenance has been performed. Corrosive water

conditions, and/or unauthorized adjustments or repair could render

the product ineffective for the service intended. Regular checking

and cleaning of the product’s internal components helps assure

maximum life and proper product function.

WARNING

!

** Metric Dimensions are nominal pipe diameter. This product is

produced with NPT threaded end connections.