Appendix a — wshp screen open configuration (cont) – Carrier AQUAZONE 50RTP03-20 User Manual

Page 54

Advertising
background image

54

APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

LEGEND

SCREEN NAME

PASSWORD

LEVEL

POINT NAME

EDITABLE

RANGE

DEFAULT

NOTES

Configuration

Service

Configuration

Admin Password

level access only

# of Fan Speeds

X

1,2,3

3

Used to set number of

fan motor speeds

G Output Type

X

Fan On/Fan Low

Fan On

When set to Fan On, G output is

energized when ever any fan speed
is active (required for ECM and Fan

control board). When set to Fan

Low, output is only energized for

Low Speed

Compressor Stages

X

One Stage/Two Stages

One Stage

Defines the number of

stages of compression

Reversing Valve Type

X

O type output/B type output

O type

Determines reversing valve

signal output type

Leaving Air Auxiliary

Heat Type

X

None/2-Position HW/1 Stage

Electric/Modulating HW

None

Determines Auxiliary

Reheat Coil Type

Entering Air Water

Economizer Type

X

None/2-Position/Modulating

None

Determines Entering Air

Economizer Coil Type

2-Position Water

Valve Type

X

Normally Closed/Normally Open

Normally

Closed

Determines type of 2-position

water valve used

Modulating Water

Valve Type

X

Normally Closed/Normally Open

Normally

Closed

Determines type of modulating

water valve used

Ventilation Damper

Type

X

None/2-Position/DCV

None

Determines type of ventilation

damper control to be used

Damper Actuator Type

X

(0-10 volt)/(2-10 volt)

0-10 volt

Used to determine ventilation

damper output signal range

(closed - open)

Humidity Sensor

X

None/Installed

None

Set to Installed if humidity

sensor is present

Factory Dehumidifica-

tion Reheat Coil

X

None/Installed

None

Set to Installed if factory-installed

dehumidification reheat coil

is present

Occupancy

Input Logic

X

Occupied Open/Occupied Closed

Occupied

CLOSED

Used to determine external occu-

pancy switch contact occupied state

Condensate Switch

Alarm Delay

X

5 - 600 seconds

10 sec

Delay before equipment alarms on

high condensate level

Condensate Switch

Alarm State

X

Alarm OPEN/Alarm CLOSED

Alarm

CLOSED

Determine Alarm state of

condensate switch input

Minimum Condenser

Water Temperature in

Heating

X

25 - 60

F

60

F

Determines the minimum

acceptable water loop temperature

to start heating

Maximum Condenser
Water Temperature in

Heating

X

65 - 100 F

90 F

Determines the maximum

acceptable water loop temperature

to start heating

Minimum Condenser

Water Temperature in

Cooling

X

30 - 60

F

60

F

Determines the minimum

acceptable water loop temperature

to start cooling

Maximum Condenser
Water Temperature in

Cooling

X

85 - 120 F

95 F

Determines the maximum

acceptable water loop temperature

to start cooling

IAQ sensor

minimum input

X

0 - 5 ma

4 ma

Minimum output current (mA)

for IAQ sensor

IAQ sensor

maximum input

X

5 - 20 ma

20 ma

Maximum output current (mA) for

IAQ sensor

IAQ sensor

minimum output

X

0 - 9999 ppm

0 ppm

Corresponding value in ppm for

minimum output current

IAQ sensor

maximum output

X

0 - 9999 ppm

2000 ppm

Corresponding value in ppm for

maximum output current

BAS — Building Automation System
DCV — Demand Controlled Ventilation

ECM — Electronically Commutated Motor

IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration