I. Operating characteristics:

1. Unit shall operate using refrigerant R-22.
2. Unit shall be designed for indoor suspended

horizontal mounting and operation.

J. Electrical Requirements

Unit shall have single point power connection to
leads in terminal box.

K. Special Features:

Certain standard features are not applicable when
the features designated by * are specified. For assis-
tance in amending the specifications, your local
Carrier Sales Office should be contacted.

* 1. Electric Heat Module:

a. Provides encased heater elements that shall

attach directly to the base unit discharge.

b. Shall have bottom access.
c. UL listed.

2. Thermostat Assembly:

Provides cooling and fan control. Standard sub-
base shall include ‘‘Compressor malfunction
light’’ designed to illuminate if compressor lock-
out is activated.

3. Time Guard® II Device Compressor Cycle

Delay:
Prevents compressor from restarting for a mini-
mum of 5 minutes after shutdown.

* 4. Condensate Pump:

Unit shall be equipped with remotely located
condensate pump. A field-installed light shall
illuminate when reservoir rises above a preset
level. Unit shall shut down upon reservoir light
illumination.

* 5. Head Pressure Control Package:

Allows unit to mechanically cool down to 0° F
ambient temperature. Package shall include
damper operating device and all necessary
hardware.

6. Vibration Isolation Package:

Shall provide 4 spring hangers for ceiling
mounted unit to damper vibration that may be
transmitted to building structure.