Carrier 012 User Manual

Page 16

Advertising
background image

Table 10 — Fan Performance (English), 50LJQ008 (50 Hz) — Horizontal Discharge Units

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

2200

459

0.42

549

0.62

625

0.83

691

1.06

753

1.31

805

1.58

842

1.87

857 2.16

851 2.45

823 2.70

2400

482

0.50

569

0.71

645

0.95

708

1.18

768

1.40

824

1.72

872

2.01

909 2.32

931 2.64

935 2.96

2600

507

0.59

592

0.82

663

1.08

727

1.32

784

1.58

839

1.87

891

2.17

936 2.49

973 2.82

999 3.16

2800

533

0.71

615

0.95

683

1.20

747

1.49

802

1.75

855

2.04

906

2.35

954 2.67

997 3.01 1034 3.36

3000

559

0.83

637

1.09

704

1.35

765

1.66

823

1.94

872

2.22

921

2.54

969 2.88 1014 3.22

3200

585

0.96

660

1.24

727

1.52

785

1.83

841

2.15

892

2.45

939

2.76

984 3.10

3400

610

1.10

682

1.41

750

1.72

806

2.01

860

2.36

912

2.69

958

3.01 1002 3.34

3600

636

1.25

707

1.60

772

1.93

828

2.23

880

2.57

930

2.95

978

3.29

3800

661

1.41

733

1.82

795

2.15

852

2.48

901

2.80

949

3.20

Table 11 — Fan Performance (English), 50LJQ012 (50 Hz) — Horizontal Discharge Units

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

3000

484

0.55

560

0.70

631

0.87

690

1.03

747

1.20

800

1.38

850

1.52

879 1.38

925 1.81

964 1.92

3200

505

0.66

579

0.81

646

0.98

708

1.16

761

1.34

812

1.51

862

1.71

908 1.85

944 2.01

984 2.09

3400

527

0.78

599

0.93

664

1.11

724

1.30

775

1.48

827

1.67

873

1.85

920 2.07

963 2.21 1001 2.31

3600

548

0.92

619

1.05

680

1.24

738

1.43

794

1.64

840

1.83

888

2.04

931 2.23

976 2.47 1017 2.62

3800

571

1.08

639

1.19

698

1.39

756

1.60

810

1.81

856

2.02

901

2.23

945 2.44

986 2.65 1029 2.89

4000

593

1.25

659

1.35

717

1.56

773

1.78

823

1.98

875

2.22

915

2.42

960 2.65 1000 2.87 1039 3.10

4200

616

1.45

680

1.53

737

1.74

789

1.95

841

2.18

889

2.41

934

2.65

972 2.87 1015 3.12 1053 3.34

4400

639

1.67

701

1.73

757

1.92

807

2.16

858

2.41

903

2.62

951

2.89

990 3.12 1028 3.36

4600

662

1.91

722

1.95

777

2.13

827

2.38

874

2.62

921

2.87

965

3.11 1008 3.39

4800

686

2.17

744

2.20

797

2.36

846

2.62

891

2.85

938

3.14

980

3.37

5000

710

2.45

766

2.47

816

2.61

866

2.86

910

3.12

934

3.39

Table 12 — Fan Performance (English), 50LJQ008 (50 Hz) — Vertical Discharge Units

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

2200

503

0.50

585

0.71

653

0.92

716

1.15

772

1.38

824

1.63

884 1.95

934 2.30

916 2.64 1019 3.09

2400

534

0.61

613

0.84

677

1.06

738

1.30

794

1.55

844

1.81

892 2.08

944 2.40

987 2.76 1039 3.20

2600

565

0.74

639

0.97

703

1.20

761

1.46

816

1.74

866

2.01

913 2.29

957 2.58 1004 2.91 1050 3.31

2800

597

0.89

665

1.12

731

1.40

786

1.66

839

1.93

889

2.23

935 2.52

978 2.62 1019 3.13 1061 3.47

3000

629

1.06

694

1.29

759

1.59

812

1.88

862

2.15

911

2.46

957 2.78 1000 3.09 1040 3.41

3200

662

1.25

724

1.50

785

1.80

840

2.11

887

2.41

934

2.71

980 3.04 1022 3.38

3400

696

1.46

756

1.73

811

2.02

868

2.37

914

2.69

959

3.00 1003 3.32

3600

729

1.69

787

1.98

839

2.27

894

2.64

942

2.99

984

3.32

3800

763

1.95

819

2.27

869

2.56

920

2.92

970

3.31

Table 13 — Fan Performance (English), 50LJQ012 (50 Hz) — Vertical Discharge Units

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

3000

532

0.64

605

0.81

670

0.97

725

1.12

778

1.28

825

1.43

874 1.60

926 1.82

974 2.11 1012 2.36

3200

557

0.75

628

0.93

690

1.10

746

1.28

796

1.44

844

1.61

888 1.70

934 1.94

988 2.18 1025 2.47

3400

583

0.88

651

1.06

711

1.25

767

1.44

815

1.61

863

1.79

907 1.97

947 2.14

991 2.32 1038 2.57

3600

609

1.01

674

1.22

732

1.42

787

1.61

836

1.80

880

1.98

926 2.18

966 2.36 1004 2.54 1045 2.74

3800

535

1.16

698

1.39

755

1.59

808

1.80

857

2.01

901

2.20

943 2.39

985 2.60 1023 2.79 1059 2.98

4000

662

1.33

722

1.57

778

1.78

829

2.01

878

2.22

922

2.44

962 2.63 1003 2.84 1042 3.06 1078 3.26

4200

689

1.52

746

1.77

801

1.99

851

2.23

898

2.45

943

2.69

983 2.91 1021 3.11 1060 3.34

4400

715

1.72

772

1.99

825

2.22

873

2.46

919

2.71

963

2.94 1004 3.19 1042 3.41

4600

742

1.94

797

2.22

848

2.48

896

2.72

940

2.98

984

3.22 1025 3.48

4800

770

2.18

823

2.46

872

2.75

919

3.00

963

3.27

5000

797

2.44

849

2.73

897

3.04

943

3.30

LEGEND

Rpm — Wheel Speed (Revolutions per Minute)
Bhp

Fan Shaft Power (Brake Horsepower)

NOTES:
1. Boldface indicates field-supplied drive required.

2.

indicates field-supplied motor and drive required.

3. Maximum usable output power (Bhp) on the 50LJQ008 unit is 2.40

(1.79 BkW) with standard 1.5 hp (1.12 BkW) motor. The maximum
usable output power (Bhp) increases to 2.90 Bhp (2.16
BkW) on the 50LJQ012 unit with standard 2 hp (1.5 BkW) motor.

Extensive motor and electrical testing on the Weathermaker I units
ensures that the full power range of the motor can be utilized with
confidence. Using the fan motors up to the power ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.

4. Use of field-supplied motor may affect wire sizing. Contact

Carrier representative to verify.

5. Values include losses for filters, unit casings, and wet coils.
6. Motor drive range is 622 to 882 rpm (10.30 to 14.70 r/s) on the

50LJQ008 and 692 to 896 rpm (11.50 to 15.00 r/s) on the 50LJQ012.
All other rpms (r/s) will require a field-supplied drive.

16