Wiring, Isfs-02 kit vs. applicable heater model number, Figure 4 figure 5 – Chromalox ISFS-02 User Manual

Page 2

Advertising
background image

2150 N. RULON WHITE BLVD., OGDEN, UT 84404

Phone: 1-800-368-2493 www.chromalox.com

WIRING

The basic stock heater wiring diagram (Figure 4) will be changed
to the finished diagram (Figure 5).

1. Remove the motor lead wires from the heater contactor terminals

marked T1, T2 and T3. (Note that single phase motors will have
only two lead wires.)

2. Connect the black wire (Number 1) from the switch to the T3 ter-

minal on the heater contactor.

3. Connect black wire (Number 3) to contactor terminal marked L3.
4. Connect one of the motor leads to terminal 2 on the switch.
5. Connect the second motor lead to connector terminal marked L1.

ADDITIONAL STEPS FOR HEATERS WITH
THREE (3) PHASE MOTORS

6. Connect black wire (number 9) to contactor terminal marked L2.
7. Connect black wire (number 7) to contactor terminal marked T2.
8. Connect third motor lead wire to terminal 8 on the switch. After

completion of the heater installation, when the fan circuit is first
turned on, check the rotation of the fan to be sure air is moving
from the back of the heater to the front. If the air is moving in the
opposite direction, interchange any two motor lead connections to
correct the air flow direction.

X1

X2

H2

H1

C1

Motor

1Ø or 3Ø

L3
L2

L1

T1 T2 T3

3Ø Wiring Only

Power

60Hz

Cutout

XFMR

Optional Thermostat
Built-in or Field Installed

To Element Wiring

3 Phase Delta

C1

T1 T2 T3

L1 L2 L3

C1

T1 T2 T3

L1

L3

1 Phase 2 or 3 Element

Optional Disconnect Switch

Built-in or Field Installed

Built-in or Field Installed
Factory Wiring

Transformer Color Code Index

Pri.
Volt

Pri.

Lead

XFMR

Clrs.

120V

Lead

Sec.

Clrs.

24V

Lead

Sec.

Clrs.

208

240

277

480

H1

H2

X1

X2

X1

X2

WHT

WHT

WHT

WHT

BLK RED

RED RED

RED

RED RED

RED

RED

RED YEL

YEL

YEL

YEL

YEL

YEL

YEL

YEL

YEL

BLU

X1

X2

Motor

1Ø or 3Ø

L3
L2

L1

3Ø Wiring Only

Power

60Hz

Cutout

XFMR

Optional Thermostat

Built-in or Field Installed

To Element Wiring

3 Phase Delta

C1

T1 T2 T3

L1 L2 L3

C1

T1 T2

T3

L1

L3

1 Phase 2 or 3 Element

Optional Disconnect Switch

Built-in or Field Installed

Built-in or Field Installed
Factory Wiring

Transformer Color Code Index

Pri.
Volt

Pri.

Lead

XFMR

Clrs.

120V

Lead

Sec.

Clrs.

24V

Lead

Sec.

Clrs.

208

240

277

H1

H2

X1

X2

X1

X2

WHT

WHT

WHT

BLK RED

RED RED

RED RED

RED

RED YEL

YEL

YEL

YEL

YEL

YEL

YEL

C1

T1 T2 T3

Motor

1Ø or 3Ø

Standard Motor Connection

C1

T1 T2 T3

H1

H2

3Ø Wiring Only

1
3

2

7

9

8

10
12

11

Optional Summer
Fan Switch Built-in
or Field Installed

Figure 4

Figure 5

ISFS-02 Kit vs. Applicable Heater Model Number

MODEL

LUH-D-02-81-34-00
LUH-D-02-21-34-00
LUH-D-02-71-35-00

LUH-D-04-81-34-00
LUH-D-04-83-34-00
LUH-D-04-21-34-00
LUH-D-04-23-34-00
LUH-D-04-71-35-00

LUH-D-05-81-34-00
LUH-D-05-83-34-00
LUH-D-05-21-34-00
LUH-D-05-23-34-00
LUH-D-05-71-35-00

LUH-D-07-81-34-00
LUH-D-07-83-34-00
LUH-D-07-21-34-00
LUH-D-07-23-34-00
LUH-D-07-71-35-00

MODEL

LUH-D-10-81-34-00
LUH-D-10-83-34-00
LUH-D-10-21-34-00
LUH-D-10-23-34-00

LUH-D-12-83-34-00
LUH-D-12-23-34-00

LUH-D-15-83-34-00
LUH-D-15-23-34-00

LUH-D-20-23-34-00

LUH-D-30-83-34-00
LUH-D-30-23-34-00

LUH-D-35-23-34-00

LUH-D-40-23-34-00

MODEL

KUH-C-02-81-00
KUH-C-02-21-00
KUH-C-02-71-00

KUH-C-04-81-00
KUH-C-04-83-34
KUH-C-04-21-00
KUH-C-04-23-34
KUH-C-04-71-00

KUH-C-05-81-00
KUH-C-05-83-34
KUH-C-05-21-00
KUH-C-05-23-34
KUH-C-05-71-00

KUH-C-07-81-34
KUH-C-07-83-34
KUH-C-07-21-34
KUH-C-07-23-34
KUH-C-07-71-30

MODEL

KUH-C-10-81-34
KUH-C-10-83-34
KUH-C-10-21-34
KUH-C-10-23-34

KUH-C-12-83-34
KUH-C-12-23-34

KUH-C-15-83-34
KUH-C-15-23-34

KUH-C-20-23-34

KUH-C-30-83-34
KUH-C-30-23-34

KUH-C-35-23-34

KUH-C-40-23-34

Limited Warranty:

Please refer to the Chromalox limited warranty applicable to this product at

http://www.chromalox.com/customer-service/policies/termsofsale.aspx.

Advertising