WIRING

WARNING: Hazard of Shock. Any installation involving
electric heaters must be effectively grounded in
accordance with the National Electrical Code to elim-
inate shock hazard.

1. Electrical wiring to heater must be installed in accordance with the

National Electrical Code and local electrical codes by a qualified
person as defined in the NEC.

2. Because of the high operating temperatures expected, aluminum

wiring is not recommended.

3. Refer to wiring Diagram Figure C for typical wiring used for con-

necting the NWHO-27 series heater.

4. Three 3 phase circuits is a typical design for these heaters. Other

circuit arrangements are often supplied depending upon customer
specifications or amperage rating. Check engineering drawing for
specific wiring diagram of custom orders.

OPERATION

1. Do not heat materials that are corrosive to the heating element

sheath or chamber. For oil heating service, condensate drain may
be provided from bottom of chamber. Check factory.

2. Terminal ends of heater must be protected from drippings conden-

sation, spray or direct spill-over of material whose presence at the

terminals may damage heater’s electrical insulation. Liquid-tight
terminal enclosures are available to protect heater. Check factory.

3. If foreign material is carried by the oil flow, install suitable filters

in the inlet pipe to the heater.

4. Do not allow heater to operate when fluid flow is interrupted.

MAINTENANCE

WARNING: Hazard of Shock. Disconnect all power
before servicing heater.

1. Remove heating element assembly periodically to check heater

sheath for corrosion or excessive oxidation. Correct operating con-
ditions to minimize sheath deterioration.

2. Periodically check temperature control and pressure temperature

safety limit control operation to insure accurate and safe process
operation.

3. Check all electrical connections periodically and retighten connec-

tions which may have loosened in service. Replace wire terminals
which show signs of oxidation which would interfere with estab-
lishment of reliable electrical connections.

RENEWAL PARTS IDENTIFICATION

Order Renewal Parts on a Special Order Basis. Give the name of the part number, voltage, and wattage to your Chromalox Representative for
identification of renewal parts.

2150 N. RULON WHITE BLVD., OGDEN, UT 84404

Phone: 1-800-368-2493 www.chromalox.com

TA - U0 - EF

Litho in U.S.A.

3L1

3L2

3L3

2L1

2L2
2L3

1L1

1L2

1L3

Figure C — 240V, 480V, 3 Phase 3 Circuits