Environmental

Storage

1.87 G

rms

at 10 Hz to 500 Hz for 15 min (all six sides

tested).

Maximum Shock

Operating

One shock pulse in the positive z axis of 31 G for 2.6
ms in all operational orientations.

Storage

Six consecutively executed shock pulses in the
positive and negative x, y, and z axes (one pulse on
each side of the system) of 71 G for up to 2 ms.

Maximum Altitude

Operating

3048 m (10,000 ft)

Storage

12,000 m (39,370 ft)

Operating Altitude De-rating

Up to 35 °C (95 °F)

Maximum temperature is reduced by 1 °C/300 m (1
°F/547 ft) above 950 m (3,117 ft).

35 °C to 40 °C (95 °F to 104 °F)

Maximum temperature is reduced by 1 °C/175 m (1
°F/319 ft) above 950 m (3,117 ft).

40 °C to 45 °C (104 °F to 113 °F)

Maximum temperature is reduced by 1 °C/125 m (1
°F/228 ft) above 950 m (3,117 ft).

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous
pollution are beyond the limits specified below and are the reason for the damage and/or failures
to your equipment, it may be necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental conditions is the
responsibility of the customer.

Air Filtration

NOTE: Applies to data center
environments only. Air filtration
requirements do not apply to IT
equipment designed to be used outside a
data center, in environments such as an
office or factory floor.

Data center air filtration as defined by ISO Class 8
per ISO 14644-1 with a 95% upper confidence limit

NOTE: Air entering the data center must have
MERV11 or MERV13 filtration.

Conductive Dust

NOTE: Applies to data center and non-
data center environments.

Air must be free of conductive dust, zinc whiskers,
or other conductive particles.

Corrosive Dust

NOTE: Applies to data center and non-
data center environments.

• Air must be free of corrosive dust.
• Residual dust present in the air must have a

deliquescent point less than 60% relative

humidity.

8