Dell UPS 5600R User Manual
Page 63
63
Specifications
|
Table 14. Battery
Configuration
5600W: (18) 216V, 7.2 Ah internal batteries; (18) 216V, 7.2 Ah EBM
Battery Type
CSB GP1272 7.2 Ah or YUASA NP7-12 7Ah
Voltage
5600W: 216 Vdc internal, 216 Vdc/30A EBM
Fuses
UPS: (2) 30A fuses
EBM: (2) 30A fuses
Type
Sealed, maintenance‐free, valve‐regulated, lead‐acid
Charging
Approximately 4 hours to 90% usable capacity at nominal line and no
supplementary power supply load
Monitoring
Advanced monitoring for earlier failure detection and warning
Battery Runtimes*
5600W internal batteries: 5.5 minutes at full load/17 minutes at half load
5600W with one EBM attached: 19 minutes at full load/45 minutes at half load
* Battery runtimes are approximate and vary depending on the load configuration and battery charge.
Battery
DC/DC
Input
Filter
Output
Filter
Bypass
Charger
DC/AC
Inverter
AC/DC
Boost
Output
Input
DC Bus
Figure 27. 5600W Line-Interactive UPS Block Diagram