Job-specific (50 or 60), 99 (50lr4060, 64lr4060) 1.030 (41lr4060), Job-specific – Carrier D2-3466-2 User Manual

Page 15: 03 x motor nameplate amps, Job-specific (57 or 69), 60 (50lr4060, 64lr4060) 135 (41lr4060), 505 (50lr4060, 64lr4060) 0.503 (41lr4060), Hapter, Identifying parameter defaults for carrier drives

Advertising
background image

Identifying Parameter Defaults For Carrier Drives

4-1

C

HAPTER

4

Identifying Parameter Defaults

For Carrier Drives

Use the following table to identify and set the parameter defaults for Carrier drives.

Important:

Setting P.050 (Restore Defaults) to ON will restore the drive to Reliance defaults,
not Carrier defaults. If this has been done, set the following parameters to restore
Carrier defaults

.

For job-specific parameters, refer to the 19XR, XRV Start-Up, Operation, and Maintenance
Instructions manual (531-982) for further instructions. For descriptions of all parameters, refer to
the LiquiFlo Software Start-Up and Reference manual (D2-3410).

Parameter No.

Parameter Name

Setting

P.000 Control

Source

rE

P.001

Accel Time 1

8

P.002

Decel Time 1

20

P.003

Minimum Speed

0.5

P.004

Maximum Speed

Job-specific (50 or 60)

P.005

Current Limit

110

P.009

1

1

These parameters must be tuned or calibrated per the VFD Control Verification procedures (running and

non-running) found in the Carrier 19XR/XRV Start-Up, Operation, and Maintenance Instructions on pages
59-60.

Terminal Strip Analog Input Offset

-10

P.010

1

Terminal Strip Analog Input Gain

0.99 (50LR4060, 64LR4060)

1.030 (41LR4060)

P.011

Terminal Strip Analog Input Configure

4

P.013

Output Relay Configuration

2

P.027

Forward/Reverse Configuration

1

P.028

Speed Display Scaling

Job-specific

P.043

Fault Auto Reset Attempts

10

P.044

Fault Auto Reset Time

30

P.052

AUTO/MAN Key Disable

ON

H.000

Motor Nameplate Volts

Job-specific

H.001

Motor Nameplate Base Frequency

Job-specific

H.002

Motor Nameplate Amps

1.03 x Motor Nameplate Amps

H.021

AC Line Volts

Job-specific

H.022

Overfrequency Limit

Job-specific (57 or 69)

r.001

Analog Output 1 Source

4

r.002

1

Analog Output 1 Offset

60 (50LR4060, 64LR4060)

135 (41LR4060)

r.003

1

Analog Output 1 Gain

0.505 (50LR4060, 64LR4060)

0.503 (41LR4060)

r.035

Relay Output 1 (NO) Configuration

5

r.036

Relay Output 2 (NO/NC) Configuration

2

r.037

Relay Output 3 (NO/NC) Configuration

1

r.046

Relay Output 3 Delay Time

-999

r.050

Speed Detection Level 1

35

Advertising