UVS27 Vent-Free Gas Heater

20007068

Firebox weight / shipping

110 lbs.

The installation of your Vermont Castings stove
must conform with local codes, or in the absence of
local codes, with the National Fuel Gas Code ANSI
Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do
not derate this appliance for altitude up to 4,500 feet
(1,370m). Maintain the manifold pressure at 3.5” w.c.
for Natural Gas and 11.0” w.c. for LP Gas.

UVS27R & UVS27M Vent-Free

Certified to:

ANSI Z21.11.2b-2004

Unvented Heaters

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration from elevations up to
4,500 feet (1,370m) above sea level.
Nuisance outages may occur at altitudes above
4,500 feet (1,370m) if dirt, dust, lint and/or cob-
webs are allowed to accumulate on burner and/
or ODS pilot. Monthly inspection and cleaning
is recommended for altitudes above 4,500 feet
(1,370m)
For elevations above 4,500 feet (1,370m), instal-
lations must be in accordance with the current
ANSI Z223.1/NFPA 54 and/or local codes having
jurisdiction.

WARNING: Improper installation, adjust-
ment, alteration, service or maintenance
can cause injury or property damage. Refer
to this manual for correct installation and
operational procedures. For assistance or
additional information consult a qualified
installer, service agency, or the gas supplier.

Odor During Operation

Neither natural gas nor propane gas give off an odor
when burned. The nature of a vent free combustion
system, however, is such that odors may occasional-
ly be produced during heater operation when impuri-
ties exist in the immediate area. Cleaning solutions,
paint, solvents, cigarette smoke, candles, adhesives,
new carpet or textiles, etc., all can create fumes.
These fumes may mix with combustion air and can
create odor. Such odors will disappear over time,
however the condition can be alleviated by opening a
window or otherwise providing additional ventilation
to the area.

Inlet Minimum

5.5” w.c.

11” w.c.

Inlet Maximum

14” w.c.

14” w.c.

Manifold Pressure

3.5” w.c. 10” w.c. (MP)

11” w.c. (RP)

Gas Inlet and Manifold Pressures

Natural

LP (Propane)

WARNING:

Failure to keep the primary air opening(s) of the
burner(s) clean may result in sooting and property
damage.

Gas Specifications

Max.

Min.

Gas

Input

Input

Air

Model

Fuel Control BTU/h BTU/h Shutter*

UVS27RN

Nat

Millivolt 28,000 19,500

Fully

Closed

UVS27RP

Prop Millivolt 28,000 19,500

n/a

UVS27MN

Nat

Millivolt 28,000 19,500

Fully

Closed

UVS27MP

Prop Millivolt 28,000 19,500

n/a

*Natural Gas units with Glass & Catalyst installed; air
shutter is fully closed and rotated with bend outside of
burner for less restriction. Propane units have no air
shutter.