INSTALLATION

The Marley Engineered Products radiant heater is shipped

fully assembled. The heater can be hung from the ceiling with 4

chains or rigid angle brackets attached to the heater brackets

located on the back of the heater, for 2 and 4.5 kW heaters,

chains can be attached to the four holes in the corners of the back

reflector. Optional hanging chain kits are available for these

heaters that will allow for installations 2 to 6 feet from the ceiling.

(Model MHK) (See Figure 1.) Minimum spacings:

Ceiling to top of heater is 2 feet.

Wall to sides of heater is 3 feet.

Floor to bottom of heater is 10 feet.

NOTE: Installer should consult state and local codes and meet

any applicable requirements regarding this installation.

1. Use heater only at the voltage specified on the nameplate.

2. Branch circuit wire for connection to heater must be at least

90°C wire. Use copper conductors only.

3. Heater can be wired with rigid or flexible conduit.

4. Refer to Table 1 for proper supply wiring size.

5. The heater connection points are located in the gasketed

terminal enclosure. To remove cover, remove 4 screws on the

cover. Remove the cover to expose wiring connection points.

6. A green ground terminal is provided in the bottom of the

enclosure. The ground wire should be connected before other

connections are made.

7. Attach power to pigtail leads L1 and L2 (or L1, L2 & L3 on 3

phase models) using appropriate listed connectors.

NOTE: All 3 element heaters are factory pre-wired for 3-phase

delta operation. Some units can be converted to single phase

operation by changing the wiring. Refer to Table 1 for those

heaters that can be converted to single phase. The appropriate

wiring diagram (Figure 2) is also located on the bottom of the

enclosure.

INSTRUCTIONS FOR FIELD CONVERSION

FOR 3 PHASE TO 1 PHASE

1. Remove nuts from all terminals.

2. Remove all pigtail leads and hat shaped buss bar.

3. Remove end of lead wire on terminal 5 and slip onto

terminal 4.

4. Remove lead wire attached to instruction sheet and connect

between terminals 4 and 6.

5. Install hat shaped buss bar between terminals 3 and 5.

6. Place pigtail lead marked “L1” on to terminal 2 and pigtail lead

marked “L2” on to terminal 6.

7. Install nuts and tighten.

8. Connect entrance wiring to pigtail leads “L1” and “L2”. Connect

ground to screw provided.

9. Inspect to make sure wiring is per “Single Phase Wiring”

above.

2

ELECTRIC SHOCK HAZARD. Disconnect all power before

installing or servicing heater. Failure to do so could result in

personal injury or property damage. Heater must be effectively

grounded in accordance with the National Electrical Code,

NFPA 70.

All electrical wiring must be done by a qualified person in

accordance with National Electrical Code (NEC) and meet all

state and local regulations.

a

Figure 2

WARNING

!

TOP VIEW

SIDE VIEW

Wall

Wall

Wall

Floor -

Non-combustible surface

Ceiling

Chain

Heater

3' (914.4mm) Min.

5' min

(1524mm)

2' (609.6mm) Min.

10' (3048mm) Min.

5' min

(1524mm)

Area must be

kept clear of

combustible

materials

5' min

(1524mm)

3' (914.4mm) Min.

No Storage Area

Figure 1

FIRE HAZARD. Radiant heaters are capable of developing

high temperatures, care should be taken to:

A. Mount heater with the proper clearance between heater and

walls, ceiling and floor. B. Mount heater in horizontal position

only. Do not mount vertically or tilted in any direction. C. Do not

mount heater over combustible surfaces. D. Do not stack or

store combustible materials directly below the heater or in the

space a distance of 5 feet from any projected edge of the

heater. E. Do not operate the heater without Ground Fault

Equipment protection. Failure to follow these instructions can

result in personal injury and fire.

a

WARNING

!

FIRE HAZARD. Electric radiant heaters operate at very high

temperaures and many factors determine element life. At end of

life a radiant element in many instances will passively open cir-

cuit, however it is possible to have an arc failure that will result

in molten metal falling from the heater. To prevent personal

injury from molten metal, element damage and fire, Ground

Fault Equitment Protection must be provided.