MOUNTING

SPECIFICATIONS

ELECTRIC SHOCK HAZARD. Any installation
involving electric heaters must be performed by a
qualified person and must be effectively grounded
in accordance with the National Electrical Code to
eliminate shock hazard.

Note: Electrical wiring is to be in accordance with the National
Electrical Code and local codes by a qualified person using at least
75°C (167°F) type RH, THW or equivalent insulated conductors.

1. Electrical wiring can be brought into heater through 3/4”

knockout located either in back panel or bottom of left hand
end of heater (wiring compartment).

2. Grounding conductor with green insulation, should be secured

into grounding lug located in wiring compartment.

3. Using Wiring Diagram Table B select applicable wiring dia-

gram (Figure 2-9) for proper method of connecting heater.

4. Two or more Type HCH heaters may be controlled by a com-

mon fused disconnect switch providing total branch circuit cur-
rent does not exceed 48 amperes according to National
Electrical Code.

WIRING

ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do
so could result in personal injury or property dam-
age. Heater must be installed or serviced by a
qualified person in accordance with the National
Electrical Code, NFPA 70.

1. Locate on vertical wall with length of heater positioned horizon-

tally.

2. When selecting a mounting location, the following minimum dis-

tances must be observed:
A. 6” from bottom of heater to floor to allow for adequate air flow

through the heater.

B. 6” from wall or other obstruction to right side of heater to allow

for access to 1/4 turn fasteners.

C. 12” from wall or other obstruction to left side of heater to allow

for access to controls and wire entry.

3. Avoid mounting heater in a recess since such mounting interferes

with free air circulation, increases heater temperatures, and pre-
vents proper thermostat operation.

4. Remove front cover by giving two fasteners on right end of heater

1/4 turn then sliding cover approximately 1” to right, then lifting.

5. At the correct height for the top of the heater, draw a pencil line on

the wall, parallel to the floor.

6. Using dimensions shown in Figure 1, mark the mounting slot loca-

tion on the wall.

7. Mount heater to the wall by using fasteners (not furnished) to suit

the wall construction. Four 5/16 x 1” mounting slots are provided
in heater back panel. Note: If wall surface is not flat, resulting in
gap between rear case and wall in excess of 1/8” at location of fas-
teners, use metal washers to fill in gap. Tighten left hand fasteners
securely. The right hand fasteners should be pulled up snug to
allow for movement during operation to avoid expansion noise.

8. Replace cover and tighten 1/4 turn fasteners.

Wiring Diagram Figure No.

208V

240V

480V

550V

575V

600V

120V

277V

3øY

3øY

Model

(3 Wire)

(4 Wire)

3шY

3шY

3шY

HCH-051

2

8

8

2

HCH-071

2

8

8

2

HCH-101

2

8

4

8

4

2

3

9

6

HCH-151

2

8

4

8

4

2

3

9

6

9

9

9

HCH-201

2

8

4

8

4

2

3

9

6

9

9

9

HCH-251

2

8

4

8

4

2

7

5

6

9

9

9

HCH-301

8

4

9

4

2

7

5

6

9

9

9

HCH-351

8

4

8

4

2

7

5

6

5

5

5

HCH-401

8

4

8

4

2

7

5

6

5

5

5

HCH-451

8

4

8

4

2

7

5

6

5

5

5

HCH-501

8

4

8

4

2

7

5

6

5

5

5

Wiring Diagrams — Table B

2

Specifications - Table A

Voltage

Dimensions (In.)

Model

(60 Hz — AC)

Watts

Phase

A

B

HCH-051

120, 208,

500

1

240 or 277

HCH-071

120, 208,

750

1

240 or 277

HCH-101

120 or 277

1000

1

208, 240 or 480

1 or 3

24

15-7/8

120 or 277

1

HCH-151

208, 240 or 480

1500

1 or 3

550, 575 or 600

3

120 or 277

1

HCH-201

208, 240 or 480

2000

1 or 3

550, 575 or 600

3

120 or 277

1

HCH-251

208, 240 or 480

2500

1 or 3

36

27-7/8

550, 575 or 600

3

Note: Heaters with Model Numbers suffixed with the letter “M” (Ex: HCH-351M) are supplied with a Manual Reset.

Voltage

Dimensions (In.)

Model

(60 Hz — AC)

Watts

Phase

A

B

277

1

HCH-301

208, 240 or 480

3000

1 or 3

550, 575 or 600

3

36

27-7/8

277

1

HCH-351

208, 240 or 480

3500

1 or 3

550, 575 or 600

3

277

1

HCH-401

208, 240 or 480

4000

1 or 3

550, 575 or 600

3

277

1

HCH-451

208, 240 or 480

4500

1 or 3

48

39-7/8

550, 575 or 600

3

277

1

HCH-501

208, 240 or 480

5000

1 or 3

550, 575 or 600

3