Finish the wall with material of your choice. Do not
install a combustible mantel shelf less than 12” (305
mm) above the firebox grille opening. Do not install
a mantel face plate less than 6” (159 mm) from top
of grille opening. (Fig. 20)
If a combustible material is
used below a flat mantel shelf, consult your local build-
ing codes for minimum clearance from top of fireplace
opening to bottom of mantel shelf.
All joints (top, bottom and sides) where wall or deco-
rative facing material meets fireplace surround must
be completely sealed with a noncombustible material.
(Figs. 21 and 25)
NOTE: No side wall protection is required for fireplaces
installed at 45° to two (2) side walls (corner installation).

FP531

Fireplace surround detail

1/29/99 djt

Must be sealed with

noncombustible material

Mantel Shelf

Side View

Finished Wall

2 x 4 Stud

Standoff

Cast Front

See mantel drawing for

shelf-to-grille dimension

1” (25mm)

Fireplace

Front (Steel)

2 x 4 Stud

FP1200

Fig. 21 Finishing materials placement.

Brick Ledge

Noncombustible Finish Mate-

rial Only in this Area

Top View

Mantels

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting heights and widths, refer to
Figures 22 and 23. When using paint or lacquer to finish
the mantel, such paint or lacquer must be heat resistant
to prevent discoloration.

FP1398

Fig. 22 Combustible mantel minimum opening.

FP1398

wood mantels

8/18/03 djt

6"

(159mm)

Min.

12"

(305mm)

Min.

1���"

(38mm)

12"

(305mm)

Max.

Combustiible

Mantel and

Trim

Finished Wall

Header

Standoff

Noncombustible

Material

Brick Ledge

GrilleOpening

Fireplace Front

MA81

Fig. 23 Combustible mantel clearances.

MA81

rev. 8/5/97

*

1���"

Ref.

**

Combustible materials

are permitted within a

shaded area shown in

Figure 26 titled

Minimum Wall

Clearances

* 12” (305mm) from top of grille opening.
** 6” from top of grille opening.

Side Wall Protection

Adjacent combustible side walls that are within mini-
mum dimensions shown in Figure 25 of the fireplace
opening must be protected with CFM Corporation Wall
Shield Model SP40 or a specifically built wall shield
described in Figure 20.
The special wall shield design described in Figure 20 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must =1.85
minimum.