a. At least two ventilation openings at cylinder valve level shall be provided in the sidewall, equally

sized, spaced at 180˚ (3.14 rad), and unobstructed. Each opening shall have a total free area of not
less than fi” square inch per pound (7.1 cm

≈/kg) of stored fuel capacity, and not less than a total

free area of 10 square inches (64.5 cm

≈).

b. Ventilation opening(s) shall be provided at floor level and shall have a total free area of not less

than fi square inch per pound (7.1 cm

≈/kg) of stored fuel capacity and not less than a total free

area of 10 square inches (64.5cm

≈). If ventilation openings at floor level are in a sidewall, there

shall be at least two openings. The bottom of the openings shall be at floor level and the upper
edge no more than 5 inches (127 mm) above the floor. The openings shall be equally sized, spaced
at 180˚ (3.14 rad) and unobstructed.

c.

Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 inch (3.2 mm)
diameter rod.

Figure 1. LP Attachment Assembly

LP Gas Manifold Pressure

For plumbed-in LP installation, use a convertible regulator and set it for LP gas.

LP Gas Supply Pressure

Maximum line pressure for plumbed-in propane is 14” W.C psi (3.5 kPa). Minimum line pressure for
propane is 11” W.C.

LP Gas Pressure Regulator

The unit must be used with the gas pressure regulator. The regulator will control and maintain a uniform
gas pressure in the manifold. The burner orifices have been sized for the gas pressure delivered by the
regulator.

LPG Cylinder Specification

Any LP gas supply cylinder used with this firepit or fireplace must be approximately 12 inches in diame-
ter and 18 inches high. The maximum fuel capacity is 20 lbs. of propane, or 5 gallons. Full cylinder
weight should be approximately 38 lbs. (43.7 lbs. nominal water capacity.) Always use the cylinder dust
cap on the cylinder valve outlet during transport and when the cylinder is not connected to the firepit or
fireplace.