Dimming mode, Zero cross detection filter, Set the minimum dimming level – Crestron electronic Crestron iLux CLS-C6 series User Manual

Page 6: Ilux™ expansion module crestron cls-exp-dimu, Cls-exp-dimu wiring with dual feeds, Multiple cls-exp-dimu modules, Switch settings for s1 dip switch, Switch settings for s2 dip switch

Advertising
background image

iLux™ Expansion Module

Crestron CLS-EXP-DIMU

CLS-EXP-DIMU Wiring with Dual Feeds

NEUTRAL

CLS(I)-C6

CLS-EXP-DIMU

Lighting

Loads

DIM OUT

NEUTRAL

DI

M

OU

T

HO

T

NE

UT

RAL

C

O

NT

RO

L

NE

UT

RAL

LOAD 3

LOAD 2

LOAD 1

HOT

NEUTRAL



NEUTRAL

HOT

(120 (230) VAC)

HOT

(120 to 277 VAC)

Multiple CLS-EXP-DIMU Modules

DI

M

O

U

T

HO

T

NE

U

T

RA

L

CON

T

ROL

N

E

UT

RAL

DI

M

O

U

T

HOT

NEUT

RA

L

CONT

RO

L

NE

UT

RAL

NEUTRAL

CLS(I)-C6

CLS-EXP-DIMU

Lighting

Loads

LOAD 3

LOAD 2

LOAD 1

HOT

NEUTRAL



NEUTRAL

CLS-EXP-DIMU

Lighting

Loads



NEUTRAL

DIM OUT

NEUTRAL

DIM OUT

NEUTRAL

HOT

(120 to 277 VAC)

HOT

(120 to 277 VAC)

HOT

(120 (230) VAC)

3. Apply power to the line/load and turn on the

controlling device. The power indicator LED will
light indicating that power is supplied to the
module.

4. Replace the cover and cover screws.

Dimming Mode

The CLS-EXP-DIMU is capable of automatically
detecting the attached load type, and setting itself for
forward-phase (leading edge) or reverse-phase (trailing
edge) dimming accordingly. In addition, the unit can be
forced to perform forward- or reverse-phase dimming by
overriding the automatic detection.

Disabling the Auto Detect mode should not be
necessary, and is not recommended unless suggested
by a Crestron technical support representative.

WARNING: RISK OF SERIOUS PERSONAL
INJURY.
Turn off power at the circuit breaker(s) prior to
changing any switch settings. Changing settings with
power on can result in serious personal injury and damage
to the device.

The dimming mode can be changed by adjusting the S1
DIP switches as detailed in the following table.

Switch Settings for S1 DIP Switch

SW. 1 SW. 2

DIMMING MODE

LOAD TYPES

Off

Off

Auto Detect

(Default, recommended)

All

On

Off

Reverse Phase

Incandescent,
Electronic Low
Voltage

On

On

Forward Phase

Magnetic Low
Voltage, Neon/CC,
2-wire dimmable
Fluorescent

Zero Cross Detection Filter

The CLS-EXP-DIMU performs filtering to compensate
for noise on the incoming AC line. This filtering is useful
for eliminating flickering of the load caused by line noise.
If necessary, this filtering can be disabled.

Disabling the zero cross detection filter should not be
necessary, and is not recommended unless suggested
by a Crestron technical support representative.

WARNING: RISK OF SERIOUS PERSONAL
INJURY.
Turn off power at the circuit breaker(s) prior to
changing any switch settings. Changing settings with
power on can result in serious personal injury and damage
to the device.

The function of the zero cross detection filter is set using
the S2 DIP switch. Refer to the following table when
setting the zero cross detection filter.

Switch Settings for S2 DIP Switch

SW. 1

SW. 2

DESCRIPTION

Off

Off

Enable zero cross detection filter
(Default, recommended). Provides
maximum filtering under various line
noise conditions.

On

Off

Disable zero cross detection filter.
Allows rapid tracking of the AC line.
Suitable when using generators for AC
line power.

Set the Minimum Dimming Level

Certain types of loads can flicker when dimmed too low.
Adjust the FLUORESCENT OFF THRESHOLD to
prevent the CLS-EXP-DIMU from attempting to dim the
load below a certain level. To adjust:

1. Remove the cap from the FLUORESCENT OFF

THRESHOLD adjustment from the inside of the
cover (requires removal of cover as shown on
previous page).

6

iLux™ Expansion Module: CLS-EXP-DIMU Installation

Guide – DOC. 6682B