Outdoor Grille Selection

The following guidelines must be followed in the ini-

tial selection of any alternate exterior grille or louver:
1. The louver must have a minimum of 65% free area.

Free area is the minimum area of the opening in an

air inlet or outlet in which air can pass. Free Area

(%) = X/Y.

2. The louver should be attached to the wall sleeve in a

manner that will prevent recirculation of condenser

discharge air into the inlet. In most applications, baf-

fles, splitters, and/or gasket will be required between

the chassis tube end sheets and the louver to prevent

air recirculation.

The above criteria must be followed, since a louver

that is restrictive or allows recirculation will result in a

reduction of the unit’s capacity and efficiency and will

ultimately shorten the compressor life.

Hardwire Kit

Part No.: HARDWIRE-KIT-1PK
This accessory hardwire kit provides a permanent con-

nection to the unit. Electrical hard wiring is required

when NEC (National Electrical Code) or local codes

restrict the use of power cord and plug connections.

The hardwire kit mounts on the front right side of the

unit and comes with 36 inches of flexible steel conduit

and a Molex connector for easy connect/disconnect.

Conduit Interface Kit

Part No.: CONDUIT-INTF-4PK
The conduit interface accessory kit provides the wire

connection to the unit to interface to field-supplied

conduit.

IMPORTANT: If you wish to use a grille not

made by Carrier for your Carrier unit(s), con-

tact the Carrier Application Engineering Group

at 1-800-894-6449.

X

Y

X

Y

X

Y

X

Y

Sample Calculations

Free Area (%) =

x

x 100

y

x = 1

y = 1.5

F.A. (%) =

1

x 100 = 66.7%

1.5

Louver Dimensional Reference