Chromalox PQ404-6 User Manual

Installation, operation, Horizontal electric steam boiler, Renewal parts identification

Advertising
background image

(Supersedes PQ404-5)

PQ404-6

CHS

161-048642-001

OCTOBER, 1983

4

and

Installation, Operation

RENEWAL PARTS IDENTIFICATION

Horizontal Electric Steam Boiler

Model Number CHS 0 – 150 PSI

© 2010 Chromalox, Inc.

Power CC

Size of

Output

Nominal

90˚C

Amps

Standard Lbs. per

Model

B.H.P.

Fuse Delta

Size

Wire

per

Elements

Control

Hr. at

Number

Rating kW Contactors Size

kW

(Amps)

(M.C.M) Circuit

(kW)

System

212˚F

CHS-150*

15.3

150

5

50A 60A

30

1

300

4/0

181

2

60

452

1

30

CHS-180*

18.4

180

6

50A 60A

30

1

300

250

217

3

30

543

CHS-210*

21.4

210

7

50A 60A

30

1

600

600

253

3

60

633

1

30

CHS-240*

24.5

240

8

50A 60A

30

1

600

400

290

4

60

723

CHS-270*

27.6

270

9

50A 60A

30

1

600

600

326

4

60

814

1

30

CHS-300*

30.6

300

10

50A 60A

30

1

600

600

362

5

60

904

CHS-360

36.7

360

12

50A 60A

30

2

300

250

217

2

90

1085

3

60

CHS-420

42.9

420

14

50A 60A

30

2

600

350

254

4

90

1266

1

60

CHS-495

50.5

495

11

60A 100A

45

2

600

500

297

3

135

1492

1

90

CHS-540

55.1

540

12

60A 100A

45

2

600

600

324

4

135

1628

CHS-630

64.3

630

14

60A 100A

45

2

600

700

378

4

135

1889

1

90

CHS-720

73.5

720

16

60A 100A

45

3

600

400

324

5

135

2170

1

45

CHS-810

82.7

810

18

60A 100A

45

3

600

600

324

6

135

2441

CHS-945

96.4

945

21

60A 100A

45

3

600

700

378

7

135

2848

CHS-1080 110.0 1080

24

60A 100A

45

4

600

500

324

8

135

3255

CHS-1215 124.0 1215

27

60A 100A

45

4

600

700

378

9

135

3662

CHS-1350 138.0 1350

30

60A 100A

45

5

600

600

324

10

135

4069

CHS-1485 152.0 1485

3

60A 100A

45

5

600

700

378

11

135

4476

CHS-1620 165.0 1620

36

60A 100A

45

6

600

600

324

12

135

4883

Specifications — 480 Volt Boilers*

INSTALLATION

CAUTION: To avoid electrical shock hazard, boilers
must be suitably grounded to earth.
NOTE: Chromalox boilers are pre-tested before shipment; no internal
piping or wiring is necessary. WARNING: Substitution of compo-
nents or modification of wiring without prior consent of Chromalox,
Inc. voids warranty.
1. Locate unit on level floor or platform. NOTE: A minimum dis-

tance of 60 inches from wall, other equipment, etc. must be
allowed for removal of the elements.

2. Complete all piping to boiler. Connect water line to tagged fitting

on the motor and pump assembly, if used, or to tagged fitting on
water control feeder.

3. When any type of feed other than a pump feed is used – the exist-

ing water supply must be 10 pounds greater than the boiler operat-
ing pressure to assure water supply maintains proper water level in
boiler. Otherwise, lack of water can cause heater failure. Keep feed
water line valves open at all times.

4. All water feed systems are connected to supplied water inlet check

valve.

5. Connect steam line (with Globe valve) to boiler steam outlet. Valve

should be placed as close as possible to boiler outlet.

6. To insure maximum efficiency of supplied kw, all piping from out-

let should be insulated.

7. Drain and relief valve piping should be in accordance with state

and local codes.

CHS-360 Steam Boiler

*150 kW Thru 300 kW Boilers available in 280V and 240V. Check Factory

Boiler Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Circuit Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Model No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. of Power Circuits . . . . . . . . . . . . . . . Amps. . . . . . . . . . . . . . . . . . . .

Electrical Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Circuit Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

National Board No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Total Amps . . . . . . . . . . . . . . . Phase . . . . . . . . . . . . Cy . . . . . . . . . . . . .

IMPORTANT – This data file contains the National Board Registration Certificate approving your generator. It must be kept near the generator at all times.