30
|
Shielding
Pan-Type Shielding
T
YPE
:
Pan-Type Systems—Euroshield (18 ga. steel or
aluminum)
D
ESCRIPTION
:
One layer of sheet steel or aluminum, joined with
M8 screws and double-row gasket in all mating joints.
O
PERATION
:
After the enclosure has been installed, the interior finishes should
not be changed. It is important that:
1.
Liquids are not spilled on the shielding.
2.
Only ETS-Lindgren RF penetration be used through the
walls, floors, and ceiling.
3.
All screws are tightened to 90-in lb torque. If screws are
removed, they must be reinstalled with the use of a
calibrated torque wrench or screw gun.
4.
Suspended floors are earthed with bonded contact to the
shield walls. Changing this bonding could affect the
chamber performance.