– Use for Thermostat controlled supermarket cases and coolers by monitoring the Average temperature. By this method, obtain

the most accurate Thermostat setting.

– Use the High and Low pressure display to accurately set the low pressure cut-in and cut-out values for pressure controlled

cases and coolers.

– Apply the two temperature sensors, with the Manifold toggled to show the T1-T2 Differential temperature, to measure

temperature drop across a cooling coil.

– Use a wet sock over a temperature sensor to measure the Wet Bulb temperature.

SYSTEM APPLICATIONS

0

5

10

15

20

25

20

18

16

14

12

10

8

6

4

Superheat in °F

Time in Minutes

Expansion Valve Superheat
DM-2 Average Superheat

H u s s m a n n R H F A 4 D o o r F F C a s e

1 Ton Low Temp.TXC

-2 F Case Temperature

40% HeaterLoad

E-Mail: [email protected]

Web Site: www.jbind.com

CHECKING TXV SETTING

The objectives of the TXV superheat setting is to prevent

liquid refrigerant floodback to the compressor and to optimize
system operation by the use of a selected setting.

The two temperature method of measuring superheat is

not recommended because it can produce a wrong
superheat measurement, due to the effect of temperature
glide of the blended refrigerants and variations in evaporator
pressure drop.

NEW RESIDENTIAL A/C SYSTEMS

For new installations of residential A/C systems, the pre-

charge will not provide an accurate amount of refrigerant
charge because of the variation in the length of liquid and
suction line connecting to the “A” coil.

RETROFITTING SYSTEMS

Retrofitting systems to a new refrigerant can change the

TXV superheat setting. The superheat setting should be
checked before and after retrofitting to be sure the superheat
is right for the equipment.

SET SUPERHEAT
FOR “HUNTING”
TXV VALVES

In refrigeration and
air conditioning

systems, the
expansion valve often
operates to produce
an evaporator
superheat which
constantly swings up
and down in value,
called “hunting.” The
DM-2 provides the
“Average” superheat
value to use for TXV
valve adjustment.

JB INDUSTRIES INC.

Aurora, Illinois 60505 USA

®

A/C & REFRIGERATION APPLICATIONS

Contact your TXV manufacturer for the exact superheat adjust rate.

AVAILABLE REFRIGERANTS

R12
R22
R134a
R290
R401A
R401B
R402A

R403B
R404A
R406A

R407A
R407B

R413A
R414B
R416A
R417A * New addition

R422B * New addition

R422C * New addition
R422D * New addition
R427A * New addition
R428A * New addition
R438A * New addition o

R402B

R502
R507
R508B

R408A
R409A
R410A
R411C

R407C

R422A

REPLACEMENT ITEMS

PART NO.

DESCRIPTION

SH-56

Socks (5)

ACCESSORIES

SH-59 6' Temperature Sensor Clamp

SH-60 6' Temperature Sensor

w/ right elbow (made for DM)

Warranty Information:

Unit has 1 year over the counter warranty due to
Manufacturing defects with proof of purchase.
Customer abuse/neglect not related to
Manufacturing quality will void warranty.