Introduction

The HPO-0071 is an eight-circuit transient suppres-

sor board used on the inputs of digital controllers,

and the twelve-circuit HPO-0070 is used on the

outputs. When properly installed and wired, these

board can protect the digital controllers from high-

voltage transients.
These boards are required on every controller

involved in smoke control applications. (See

Smoke Control Manuals 000-035-08 (BACnet) and/

or 000-035-09 (KMDigital) for more information.)

If such a controller has more than eight inputs, an

additional HPO-0071 will be needed.

Installation Guide

I/O Transient Suppressor Boards

HPO-0070/0071

DRAFT

NOTE: W

atermark is

on nonwritable DRAFT

Watermark layer

. Turn the

layer off or delete layer

to remove from the final

document.

Illustration 1—Snap Track Installation

Illustration 2—Input Wiring with HPO-0071


���


���

����������������

���������������

��������������


���


���

����������������

����������������

�������������

�����

�����

��������

����������

������������

���

���

����������

��������

���

���

��������

�����������������

Installation and Wiring

1. Mount the (included) Snap Track in a suitable

enclosure. To avoid damaging or shorting the

board’s wiring, be sure

the mounting screw heads

do not exceed the maximum height indicated in

Illustration 1. One or two washers underneath the

track may help provide enough flex in the track to

more easily install the board.

2. Slide the boards into the Snap Track.

NOTE: Orienting the unprotected terminals on the

same side as the incoming or exiting wiring

may simplify the wiring process.

2. Connect the incoming or exiting wires to the

unprotected sides of the boards. See Illustrations

2 and 3.

3. Connect the controller wiring input and output

pairs to the corresponding protected terminals of

the boards. If the controller has more than eight

inputs, start over with Terminal 1 of the second

input board going to Input 9 of the controller.

NOTE: The SC terminals are used instead of GND

only if the controller has HPO-6701 triac

or HPO-6703/6705 relay output override

boards installed.

CAUTION

To avoid damaging or shorting the board’s
wiring, be sure the mounting screw heads
do not exceed this maximum height.