Important notices, Maintenance, Adjustments and calibration – KMC Controls CTE-1101 User Manual

Page 2: Temperature averaging

Advertising
background image

CTE-1001/1002/1101

2

Installation Guide

© 2011 KMC Controls, Inc.

800-019-02C

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com, [email protected]

Important Notices

The material in this document is for information pur-

poses only. The contents and the product it describes

are subject to change without notice. KMC Controls,

Inc. makes no representations or warranties with respect

to this document. In no event shall KMC Controls, Inc.

be liable for any damages, direct or incidental, arising

out of or related to the use of this document.

Maintenance

No routine maintenance is required. Each compo-

nent is designed for dependable, long-term reliabil-

ity, and performance. Careful installation will also

ensure long-term reliability and performance.

CTE-1101

Adjustments and Calibration

Upon receipt from the factory, no thermal calibration

should be required.

Flow control points can be calibrated before or after

installation:
1. Verify 9.1 VDC between (+) and (–) terminals. (See

the wiring diagram on the previous page.)

2. Measure T1 output voltage (via the meter taps

and HSO-5001 calibration test leads).

3. Refer to the graphs (at the right) to make

adjustments.

4. Always adjust the minimum flow first.
a. DA Cooling: Setpoint > Room Temp.
b. RA Heating: Setpoint < Room Temp.
5. Always adjust maximum limits to a value higher

than the minimum limits. If in doubt, turn Max.

limit fully clockwise (increase) before proceeding.

a. DA Cooling: Setpoint < Room Temp.
b. RA Heating: Setpoint > Room Temp.

0

1

2

3

4

5

6

-1˚F

+1˚F

CTE-1001 SPACE TEMPERATURE D.A. COOLING
CTE-1002 SPACE TEMPERATURE R.A. HEATING

SETPOINT

T3 OUTPUT, D.A.
T1 OUTPUT, D.A.

T1 & T3

VDC

OUTPUT

CTE-1101

Thermostat

CEP/CSP

Series

Controller-

Actuator

TTE-1001

Remote

Temperature

Transmitter

Temperature Averaging

For temperature averaging on a CTE-1101 (only),

connect the CTE-1101’s A, +, and – terminals to

the respective terminals on the back of the remote

transmitter.