Differential Pressure Flow Sensors

SSS-1000 Series

Mounting

1. Determine the duct’s flow direction and install

the sensor based on the sensor’s flow arrow

imprint.

NOTE: The sensor must be mounted with the

arrow pointing in the direction of the air

flow.

2. Cut a 7/8" hole in the duct to accept the sensor

probes.

3. Attach using two self-tapping screws inserted in

the 3/16" mounting holes.

Connections

Connections use 3/8" (SSS-100x) or OD polyethylene

tubing. Check that there are no sharp bends in the

tubing at any connection. Bends and creases may

leak as tubing ages.
1. Connect the Port “H” to the “High” input on the

VAV controller.

2. Connect the Port “L” to the “Low” input on the VAV

controller.

NOTE:

For using SSS-100x sensors with CSC-

3000 series, CSP-4000/5000 series,

KMD-7000 series, and BAC-7000 series

controllers, use a 3/8" to 1/4" barb union

adapter and appropriate polyethylene

tubing to the sensor and controller. For

maximum accuracy in the CSP-5000 series,

KMD-7000 series, and BAC-7000 series

controllers, the 3/8" OD tubing between the

sensor and the adapter should be as short as

possible, and the 1/4" OD tubing from the

adapter to the controller should be 24" long

(on both the High and the Low sides). OR

use the equivalent SSS-101x sensor.