STE-6014/6017/6018/6019/6020 Room Temperature Sensors

2

Installation Guide

STE-6014/6017/6018

Connecting any of these models to a KMC controller

requires a special cable with (on the sensor end) an

RJ-45 connector and (on the controller end) an RJ-11

connector with an additional three wires (as relevant

to the model) for controller inputs. Purchasing

preassembled cables from KMC is more cost-

effective and reliable than creating custom cables in

the field. Use one of the following cables:
• KMD-5693 = 25 feet
• KMD-5694 = 50 feet
• KMD-5695 = 75 feet
The three additional wire connections to the control-

ler are:
• Orange is the thermistor signal to the controller’s

appropriate input

• Orange/white is the setpoint signal to the con-

troller’s appropriate input

• Green is the supply voltage of 10 VDC to the

STE-6018 LED from an output of the controller

(for the STE-6014/6017, clip or tape the unused

wire)

NOTE: Pressing the push button (not available

on the STE-6014) momentarily shunts the

thermistor for a SENSORON signal (via the

C terminal or orange wire).

KMD-5693 = 25 feet; KMD-5694 = 50 feet; KMD-5695 = 75 feet

1

8

Orange

Wire = Thermistor

Temperature

Signal to Controller

Orange/White

Wire = 0–10K Pot

Setpoint

Signal to Controller

12 inches

5

2

RJ-11 and

Wire Leads

to Controller

RJ-45

to STE

Sensor

Green

Wire = 10 VDC

Supply Voltage

from Controller

(for STE-6018 only; cut or tape back for STE-6014/6017)

RJ-11 RJ-45 Color

(Lead) 8 Orange

7 N.C.

(Lead) 6 Green
3

5

Blue

4

4

Blue/White

5

3

Green/White

2 N.C.

(Lead) 1 Orange/White

(

Cables crossed, 20 AWG

)

Wiring

STE-6019/6020

Common (“Ground”)

Thermistor (10K Ohms)

A

B

C

Potentiometer (0–10K)

(Override

Button)

D

10 VDC LED Supply (from
Controller; for STE-6020 Only)

© 2013 KMC Controls, Inc.

866-019-04C

KMC Controls, Inc.

19476 Industrial Drive, New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

More Information

For general product infor-

mation, see the

STE-6000

Series Room Temperature

Sensors/Transmitters Data

Sheet

on the KMC Controls

web site.
For mounting consid-

erations, network con-

nection, controller con-

figuration, programming,

troubleshooting, and other

information, see the

STE-

6014/6017/6018/6019/6020

Application Guide

.

Important Notices

The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice.

KMC Controls, Inc. makes no representations or

warranties with respect to this document. In no event

shall KMC Controls, Inc. be liable for any damages,

direct or incidental, arising out of or related to the

use of this document.

Maintenance

Careful installation will also ensure long-term

reliability and performance. Remove dust as neces-

sary from holes in top and bottom. Clean with a soft,

damp cloth and mild soap.