KMC Controls CTE-3007 User Manual

Installation guide, Wiring, Low limit controllers, spdt

Advertising
background image

CTE-3016/3017/3026/3027

1

Installation Guide

Installation Guide

Low Limit Controllers, SPDT

CTE-3006/3007

Mounting

1

Wiring

1

Actuation and Reset 2
Setpoint Adjustment 2
Testing

2

Accessories

2

Maintenance

2

Specifications 2
Important Notices 2

Mounting

The controller can be mounted in any position,

but avoid locations subject to excessive vibration.

For manual reset models, position the controller to

permit convenient access to the reset button.
1. Loosen the front screw and remove the cover.
2. Using the two 3/8" mounting keyholes, mount

the case flush against the duct work or any flat

surface.

3. Install the sensing capillary in a horizontal

serpentine fashion across the downstream side of

a water coil.

4. Using HMO-4523 capillary clips (ordered

separately), support the sensing capillary

at sufficient points to prevent damage from

vibration and/or air movement.

CAUTION

Do not kink or apply excessive force to the capillary
element.

5. Make the appropriate connections to the terminal

blocks. (See the Wiring section.)

Wiring

An opening for installing a connector for 1/2" conduit

is provided in the bottom of the case.
All wiring should comply with national and local

electrical codes. Using 10 to 14 AWG solid copper

wire is recommended.
Strip wire ends 3/8", insert the wire ends under

the cup washers on the switch block, and securely

retighten terminal screws. Wire terminals according

to the Actuation and Reset section on the next page.