Adjustments and calibration, Accessories, Maintenance – KMC Controls CCE-3000 Series User Manual

Page 2: Specifications, Important notices, Adjustments and calibration 2 accessories, Specifications 2 important notices 2, Switches (see, Specifications maintenance

Advertising
background image

CCE-3000 Series

2

Installation Guide

Adjustments and Calibration

1. Choose a setpoint between 2 and 20 psi (14 and

138 kPa).

NOTE: The differential on these models is 1 psi

minimum and 2 psi maximum (7 and 14

kPa).

2. Turn the setpoint adjustment wheel until the

bottom of the wheel lines up with the signal

pressure listed beside the spring.

3. Repeat for each switch.

NOTE: A gauge may be installed before completing

Step 2 to calibrate the relay to a particular

signal pressure.

© 2012 KMC Controls, Inc.

155-019-01E

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Important Notices

The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice.

KMC Controls, Inc. makes no representations or

warranties with respect to this document. In no event

shall KMC Controls, Inc. be liable for any damages,

direct or incidental, arising out of or related to the

use of this document.

Accessories

ICI-1005

Pressure gauge

Setpoint Range

2 to 20 psi (14 to 138 kPa)

Differential

Fixed differential, 1 to 2 psi

nominal (7 to 14 kPa)

Pressure Max.

30 psi (207 kPa)

Connections

Air

3/16" (5 mm) nipples for 1/4" (6

mm) O.D. polyethylene

tubing

Electrical

1/4" quick-connect terminals

Switching Action

SPDT each stage

Electrical Ratings

25 amps each switch (non-

inductive) @ 120/240/277 VAC,

1 HP @ 125 VAC, 2 HP @ 250

VAC, 750 VA pilot duty

Weight

CCE-3001

2 oz. (57 grams)

CCE-3002

4.5 oz. (128 grams)

CCE-3003

5 oz. (142 grams)

Material

Housing

Black polycarbonate

Diaphragm

Silicone

Temperature Limits

Operating

40 to 150° F (4 to 60° C)

Shipping

–40 to 150° F (–40 to 60° C)

Approvals

UL recognized
Patent Number 4,855,545 (CEE-3002/3003)

Specifications

Maintenance

No routine maintenance is required. Careful instal-

lation will help ensure dependable, long-term reli-

ability and performance.