Wiring, More information – KMC Controls VEP-43 Series User Manual

Page 2

Advertising
background image

VEB-46/VEP-43 Series 3-Way, NPT, Control Ball Valves (1⁄2 to 21⁄2")

2

Installation Guide

© 2013 KMC Controls, Inc.

050-019-51G

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

For additional instructions on wiring, feedback selec-

tor, and actuator/signal range reset (auto-mapping),

see the

MEP-4000/4800 Series Installation Guide

or

(fail-safe)

MEP-4200/4500/4900 Series Installation

Guide

.

More Information

For non-fail-safe wiring,

auxiliary switches, feed-

back/direction selectors,

actuator/signal range reset

(auto-mapping), and other

information, see the

MEP-

4000/4800 Series Installa-

tion Guide

.

For models, specifications,

and additional information,

see the

VEB-46/VFB-46

Series Data Sheet

on the

KMC web site.

CL Wiring (MEP-4x52)

~/+

+

Control Signal

2–10 VDC

Power Supply

24 VAC/VDC

OUT (Green)

2–10 IN (White)

T

COM (Blac

k)

~24

V (Red)

+

Feedback Output
1–5 or 2–10 VDC

For information on assem-

bling a quick-mount “V”

actuator on a valve body, see

the

HPO-5074 Installation

Guide

.

For fail-safe wiring,

auxiliary switches, feed-

back/direction selectors,

actuator/signal range

reset (auto-mapping), and

other information, see the

MEP-4200/4500/4900 Series

Installation Guide

.

Wiring

NOTE: The installed actuator model is indicated

by the last two digits of the VEB valve

model number (e.g., VEB-46xxxxCK

has an MEP-4002V actuator) and the

last three digits of the older VEP valve

model number (e.g., VEP-43xxx745 has an

MEP-4002 actuator). For wiring and other

information about tri-state and other

actuators no longer sold mounted on

these valves, see the respective actuator’s

installation guide on the KMC web site.

CK/745 Wiring (MEP-4002)

NOTE: Before January 2014, MEP-40x2/48x2

models had 0–10 VDC inputs. They now

have 2–10 VDC inputs. When replacing an

older 0–10 VDC actuator with a 2–10 VDC

actuator, configure the connected controller

or thermostat output to match.

Power

Supply

~

+

Control Signal

2–10 VDC

+ Feedback Output

1–5 or 2–10 VDC