3 prerequisites, 1 cooling, 2 filler panels – Kontron OM6040 Compact User Manual

Page 37: 4 mounting, 3 prerequisites - 5, Cooling - 5, Filler panels - 5, 4 mounting - 5, Installation om6040

Advertising
background image

ID 1027-6427, Rev. 2.0

Installation

OM6040

Page 3 - 5

3.3

Prerequisites

3.3.1

Cooling

The OM6040 requires forced-air cooling which is provided by the cooling fans located on the
bottom side of the subrack in the front and rear bay areas. Adequate ambient airflow to the fan
inlet areas must be ensured. In addition, the area above the subrack must also provide for ad-
equate outlet airflow. Direct re-cycling of outlet air to the inlet area must be avoided to preclude
overheating of the system.

3.3.2

Filler Panels

Filler panels for the OM6040 are available as required. Depending on solution requirements
these components may be removed or reconfigured as necessary.

3.4

Mounting

The OM6040 is supplied with a fixed mounting panel for installation in a system cabinet. This
will require mounting hardware which is not supplied with the OM6040.

For operation of the OM6040 on a flat surface, desktop or rack shelf, there are no special
mounting fixtures. In this case, for operation ensure adequate airflow to the OM6040. Care
must also be taken to ensure that the OM6040 cannot fall off of the flat surface.

Warning!
Failure to comply with the above can result in improper operation or damage
to the OM6040 or other components installed in the OM6040.
Kontron rejects any and all liability for damage resulting from inadequate
cooling of the OM6040 or components installed in the OM6040.

Warning!
If the OM6040 is operated at temperatures above 45°C, ensure that an inlet
area and an outlet area of 1U (44.45 mm) are provided.
Failure to comply with the above may cause improper operation of or damage
to the OM6040.