Analog output calibration – Rice Lake 520 Analog Output Card Installation User Manual

Page 2

Advertising
background image

Rice Lake Weighing Systems

Analog Output Calibration

The following calibration procedure requires a

multimeter to measure voltage or current output from

the analog output module.

Note

The analog output must be calibrated after the
indicator itself has been configured and
calibrated.

1. Enter setup mode and go to the ALGOUT menu

(see Figure 4):
• Set

OFFSET

to 0% for 0–10 V output; set to

20% for 4–20 mA output

• Set mode select jumper on the analog output

board to "V" for 0-10 V output, or "I" for

4-20mA output

• Set MIN to lowest weight value to be tracked

by the analog output

• Set MAX to highest weight value to be tracked

by the analog output

2. Connect multimeter to connector J1 on the analog

output board:
• For voltage output, connect voltmeter leads to

pin 3 and 4.

• For current output, connect ammeter leads to

pins 1 and 2.

3. Adjust zero calibration: Scroll to the TWZERO

parameter. Press

to view zero value, then check

voltage or current reading on multimeter. Press and

hold or

to adjust the zero value up or down.

4. Adjust span calibration: Scroll to the TWSPAN

parameter. Press

to view span value, then check

voltage or current reading on multimeter. Press and

hold

or

to adjust the span value up or down.

5. Final zero calibration: Return to the TWZERO

parameter and verify that the zero calibration has

not drifted. Press and hold

or

to re-adjust the

zero value as required.

6. Return to normal mode. Analog output function

can be verified using test weights.

See the 520 Installation Manual, PN 68973, for more

configuration information.

XXXXXXX

ALGOUT

XXXXXXX

DIG IN

SETPTS

PROGRM

XXXXXXX

PFORMT

SERIAL

CALIBR

CONFIG

XXXXXXX

FORMAT

OFF

ON

MINNEG

10000

number

MAX

SOURCE1

GROSS

NET

ERRACT

FULLSC

HOLD

ZEROSC

XXXXXXX

VERS

TWZERO

71

number

0%

20%

OFFSET

000000

number

MIN

OFF

ON

MAXNEG

15171

number

TWSPAN

Figure 4. Analog Output Menu

Specifications

Resolution

16-bit, monotonicity over temperature

Linearity

±0.03% of full scale input

Current Output

0–20 mA or 4–20 mA (20% offset)

Maximum Load Resistance

840 Ω

Power Consumption

3.9W (max. load @ 20 mA)

Voltage Output

0–10 VDC

Minimum Load Resistance

1.2 KΩ

Power Consumption

3.9W (max. load @ 10 VDC)

Input Protection

Short circuit protection, 300W transient voltage suppression

Protection for ESD, EFT (electrical fast transients), tertiary lightning, and system-generated
transients per IEC 60001-4-2, 60001-4-4, and 60001-4-5; European Standards EN50082
and EN61000-4