Configuration

49

3.2.8

FLDBUS Menu

The FLDBUS menu is shown only if a DeviceNet, Profibus, EtherNet/IP, or ControlNet option card is installed.

The SWAP parameter on the FLDBUS menu enables byte swapping by the

iRite

BusCommand handler rather

than requiring a SWP (SWAPBYTE) instruction in the PLC. Byte swapping is enabled by default for DeviceNet

cards; for all other fieldbus cards, byte swapping is disabled by default.
The DATASIZE parameter sets the size of the BusCommand handler data transfers. The default value (8 bytes, or

4 words) matches the default data size specified in the EDS and GSD files, and used by the standard discrete

transfer commands. DATASIZE can be set to any value from 2–128 bytes (1–64 words), but the value specified

must match the data size set for the PLC Scanner I/O data size.

Figure 3-18. FLDBUS Menu

TWZERO

40
0–65535

Tweak zero. Enter tweak value to adjust the analog output zero calibration. Use a multimeter to
monitor the analog output value.

TWSPAN

59650
0-65535

Tweak span. Enter tweak value to adjust the analog output span calibration. Use a multimeter to
monitor the analog output value.

FLDBUS Menu

Parameter

Choices

Description

Level 2 submenus

SWAP

YES
NO

Specifies whether byte-swapping is enabled. For DeviceNet cards, this parameter defaults to YES;
for all other cards the default value is NO.

DATASIZE

8
2-128

Specifies the data size, in bytes, that the BusCommand handler transfers. If this parameter is set to
a value other than the default (8 bytes), ensure that it matches the Scanner I/O data size specified
for the PLC.

ALGOUT Menu

Parameter

Choices

Description

Table 3-11. Analog Output Menu Parameters

SCALES

SERIAL

FEATURE

PFORMT

SETPTS

DIG I/O

FLDBUS

VERS

SWAP

YES

NO

DATASIZE

8

data_size

If SWAP = YES