Rice Lake 920i Programmable HMI Indicator/Controller - Digital I/O Expansion Card User Manual

Page 2

Advertising
background image

2

920i

Digital I/O Expansion Card Installation Instructions

6. Ensure no excess cable is left inside the

enclosure and tighten cord grips.

7. Reconnect power to the indicator.
8. Use the DIG I/O menu to conÞgure digital I/O

as necessary. See the

920i

Installation Manual

,

PN 67887.

Figure 4.

920i

Enclosure Backplate

The

920i

automatically recognizes all installed option

cards when the unit is powered on. No hardware-speciÞc
conÞguration is required to identify the newly-installed
card to the system.

A digital I/O expansion card installed at connector J5
on the CPU board is conÞgured as slot 1; a card
installed at connector J6 is conÞgured as slot 2.

Specifications

I/O Channels

Up to 24, 5V/TTL, each software
configurable as input or output

Relay Supply Voltage

5 VDC, 1A maximum

Input Voltage

0–5.5V maximum

Digital Outputs

24mA balanced outputs with
sink/source capability

Input Protection

8-screw terminal: 300W transient
voltage supression for ESD, EFT
(electrical fast transients), tertiary
lightning, and system-generated
transients per IEC 60001-4-2,
60001-4-4, and 60001-4-5; European
Standards EN50082 and EN61000-4
Remaining I/O: 2KV HBM, 100V
machine model

I/O Connection

50-pin ribbon connector, 8-screw
terminal connector

1

3

5

14

17

16

12

9

8

7

10

11

18

15

4

2

6

13

To r q u e b a c k p l a t e s c r e w s

t o 1 5 i n - l b ( 1 . 7 N - m )