CyberPower Systems Professional Rack Mount UPS 2200VA User Manual

CyberPower Systems Tools

Advertising
background image

eu.cyberpowersystems.com

Professional Rack Mount UPS

1500VA/2200VA

User Manual

K01-1500E0C-02

SAFETY WARNINGS

(SAVE THESE INSTRUCTIONS)

This manual contains important safety instructions. Please read and follow all instructions carefully

during installation and operation of the unit. Read this manual thoroughly before attempting to

unpack, install, or operate your UPS.

This equipment can be operated by any individuals with no previous training.

The socket-outlet shall be installed near the equipment and easily accessible.

During the installation of this equipment it should be assured that the sum of the leakage currents of

the UPS and the connected loads does not exceed 3.5mA.

Attention, hazardous through electric shock. Also with disconnection of this unit from the mains,

hazardous voltage still may be accessible through supply from battery. The battery supply should be

therefore disconnected in the plus and minus pole at the quick connectors of the battery when

maintenance or service work inside the UPS is necessary.

When replacing the batteries, use batteries of the same number and type.

Do not dispose of batteries in a fire, the battery may explode.

Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes.

INSTALLING YOUR UPS SYSTEM

UNPACKING

Inspect the UPS upon receipt. The box should contain the following:UPS Unit; Rack Mount bracket

x 2; Stand x2; PowerPanel Business Edition Software Disk X 1 ; PowerPanel Software Disk X1;

Serial Interface Cable (DB-9) X 2; Serial Interface to USB Adapter X 1; Telephone Cable X 1; IEC

to IEC Power Cord X 4; UPS User Manual; PowerPanel Business Edition Software User Manual;

PowerPanel Software User Manual.

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR
EQUIPMENT

1. Insure that the equipment plugged into the battery power-supplied outlets does not exceed the

UPS unit’s rated capacity (1500VA/1000W for PR1500E, 2200VA/1600W for PR2200E). If rated
unit capacities are exceeded, an overload condition may occur and cause the UPS unit to shut
down or the circuit breaker to trip.

2. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert

Watts (W) or Amps (A) into VA by doing the calculations below. Note: The below equation only
calculates the maximum amount of VA that the equipment can use, not what is typically used by
the equipment at any one time. Users should expect usage requirements to be approximately 60%
of below value.

TO ESTIMATE POWER REQUIREMENTS

1. Watts (W) x 2.0 = VA or Amps (A) x 230 = VA
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual

requirements. There are many factors that can affect the amount of power that your computer
system will require. The total load that you will be placing on the battery-powered outlets should not
exceed 80% of the unit’s capacity.

DIRECTIONS TO MOUNT THE UPS IN THE RACK

1. Assemble the handlebars to the rack mount brackets (ears) as

shown in the figures, using the flat head screws (M4.0*8mm)

provided.

2. Assemble the two ears to the both sides of the UPS enclosure as

shown in the figures, using the flat head screws (M5.0*8mm)

provided.

3. Install the UPS at or near the bottom of the rack.

CAUTION! At least two people are required when

mounting the UPS in the rack due to its weight. The battery

pack may be removed while mounting it in the rack.

HARDWARE INSTALLATION GUIDE

1. Your new UPS may be used immediately upon receipt. However,

recharging the battery for at least four hours is recommended to

insure that the battery’s maximum charge capacity is achieved. Charge

loss may occur during shipping and storage. To recharge the battery,

simply leave the unit plugged into an AC outlet.

2. Connect the equipment to your UPS outlets. The IEC-IEC power cords

coming with the unit are used to connect your computer and monitor to

the UPS. Items such as copiers, laser printers, vacuums, space heaters,

or other large electrical devices should not be connected to the UPS.

Please make sure that the total loads of your equipments are less than

the maximum total power load of your UPS.

3. Connect the UPS and a wall outlet by using your PC power cord. Please

avoid using extension cords and adapter plugs. (To maintain optimal battery charge, leave the

UPS plugged in at all times.)

4. Press the UPS power button to turn it on. The “Power On” indicator will be illuminated in “Green”.

5. Install your software and accessories. To use the software, simply connect the enclosed serial

interface cable to the serial port on the UPS and an open serial port on the computer.

BASIC OPERATION

FRONT PANEL AND REAR PANEL DESCRIPTION

Power Switch

Press the power button to turn the UPS ON or OFF.

Test Switch

Press this button to perform a self test of your UPS. This UPS also performs a self test

automatically when powered on. After the UPS passes the test, it returns to on-line

operation. If the UPS fails the self-test, please recharge the battery for at least 4 hours

and perform another self-test. If it fails after recharging the battery, please replace the

battery. In battery mode, you can press this button to silence an audible alarm.

Power On Indicator

This LED is illuminated when the utility condition is normal and the UPS outlets are

providing “clean power”, free of surges and spikes.

AVR Indicator

This LED indicates that the UPS is operating in automatic voltage regulation mode.

When the led is illuminated continuously, it indicates input over-voltage and the UPS

unit bucks the voltage. When the led is flashed in rotation, it indicates that the UPS

unit boosts input voltage.

Using Battery Indicator

This LED illuminates during utility failure, indicating that the battery is supplying

power to the battery-power supplied outlets.

Battery Level Indicator

This indicator shows a visual indication of the battery charge. When battery capacity

is under 20%, no indicator LED will illuminate. If the battery capacity is under 20%

even after 8-hour charge, the batteries may be worn out.

Load Level Indicators

This indicator shows a visual indication of the UPS load. The load indicator LED will turn

orange if the load is between 80% and 100%. If the load is under 20%, no indicator LED

will illuminate.

Circuit Breaker Reset for Overload Protection

Resettable circuit breakers provide optimal overload protection.

Battery Backup and Surge Protection Outlets

The UPS provides 4 battery powered and surge protected outlets for

connected equipment to insure temporary uninterrupted operation

during a power failure and against surges and spikes.

Backup Power for Critical Loads

The UPS provides 2 battery powered, surge protected outlets for the

most critical connected equipment and insures temporary

uninterrupted operation of connected equipment during a power

failure.

NOTE: When the UPS is overloaded, the UPS will interrupt power

supply to the other 4 battery outlets and leave these 2 outlets for

critical loads uninterrupted.

Ethernet(RJ-45) Network Protection Ports

These ports are the protection for your computer network cables.

Serial Port to PC

Professional Rack Mount UPS provides two serial

ports to allow connection and communication

between the UPS and two computers.

The two serial ports allow connection and

communication from the DB-9 serial or USB port on

the computer to the UPS unit. These interfaces are

also compatible with the UPS service provided by

Windows 98, Windows ME, Windows 2000,

Windows NT, Windows XP, Windows Server2003

The Primary computer (with PowerPanel Business Edition install ed) is the computer that you will

use to control the UPS and make any change to the operation of the UPS. The Secondary computer

(with PowerPanel installed) is unable to exhibit any control over the UPS.

When there is a power failure, the Primary computer will start to shutdown after a user controlled

delay. Once the Primary computer shuts down, the UPS will signal the secondary computer and

initiate a shutdown. The secondary computer will then shut down. Once the secondary computer has

completed its shutdown, the UPS will power off.

IN

OUT

OUT