Rice Lake TP-232 RS-232 High Energy Serial Surge Protector User Manual

Page 2

Advertising
background image

Copyright ©2001 Rice Lake Weighing Systems. All rights reserved.

Printed in the United States of America. Specifi cations subject to change without notice.

September 2001

Contents

1.0 Introduction........................................................................................................... 1

2.0 Connections .......................................................................................................... 1

3.0 Specifi cations ....................................................................................................... 2

1.0

Introduction

The TP232 is designed to help protect against low voltage lightning strikes, power
surges, and other types of voltage disturbances. Five RS-232 signals on terminal blocks
are supported with a clamping voltage of approximately 15 volts, The TP232 offers three
stages of protection starting with a gas discharge tube followed by a series resistor and
fi nally a Transient Voltage Suppresser (TVS).

In order for a surge protector to work properly, it is important to have a good con-
nection to earth ground. The TP232 offers two terminal posts and two metal mounting
brackets which provide a good ground connection for the user. The unit has been tested
to two specifi cations at 6 kilovolts, IEC 1000-4-5: 1995 “Surge Immunity Test” and
IEEE C62.41-1991 “IEEE Recommended Practice on Surge Voltages in Low-Voltage
AC Power Circuits.” To ensure the best protection of your equipment some simple con-
nection guidelines should be followed.

Authorized distributors and their employees can view or download this manual
from the Rice Lake Weighing Systems distributor site at www.rlws.com

2.0

Connections

The following connections should be made when installing the TP232 surge protector:

• The unit should be located as close as possible to the equipment being protected.
• A good ground connection must be made between the TP232 and earth ground.
This can be done with the two terminal posts on the top of the unit or the two
mounting

brackets.

• The earth ground connection should be kept as short as possible for best
performance. As as recommendation a minimum of 10 gauge copper wire at no
more than three feet should be used (see Figure 2-1). If it is not possible to
achieve the short distance a braided cable made specifi cally for grounding purposes
should be used.
• The chassis
ground of the
equipment

should

be

connected

to

the

buildings

three

prong

plug

ground.

1

10 gauge copper wire at 3 feet
long or braided cable made
specifically for grounding
purposes.

Earth green wire ground

Protected equipment

Equipment side

Line side

TX

REC

RTS

CTS

Signal ground

TX

REC

RTS

CTS

Signal ground

Figure 2-1: Wiring Diagram

Advertising