SPECIFICATIONS

Motor: 115/1/60, 3000 RPM, 1/25 HP, 1.6 FLA, Ball Bearing Permanently Lubricated.

Fan Proving Switch: Non-adjustable set point of -.40” W.C. on pressure drop. Contacts rated for an inductive load of 6.2 FLA.

High Limit: Manual reset N/C contacts, open at 170oF + 8oF. Contacts rated at 10 FLA at 120 VAC.

Post-Purge Timer: Nonadjustable 24 VAC input, approximately 45 second post-purge delay.

Cooling Fan: 115/1/60, RPM 3200, AMPS .2, CFM 105, DB Level 50.

2

GENERAL INFORMATION

Each SS2G is electrically factory line tested before shipment.

After opening carton, inspect thoroughly for hidden damage. Impeller should rotate freely. If any damage is found notify freight
carrier and your distributor immediately and file a concealed damage claim.

INSTALLATION RESTRICTIONS

1. The SS2G may not be installed on condensing appliances.

2. The SS2G may only be installed on appliances equipped with a draft hood, draft diverter or barometric draft control.

3. The SS2G shall not be installed where flue gas temperatures exceed 650oF at its inlet. Flue gas temperature verification:

A) After 15 minutes of operation, measure flue gas temperature to verify it is not more than 650oF at SS2G inlet.

4. The electrical load controlled through the Fan Proving Switch must not exceed its nameplate ratings.

5. Vent runs of over 15 linear feet require the use of an approved, insulated vent connector to prevent problems related to condensation.

CAUTIONS

The Power Venter must be installed by a qualified installer in accordance with these instructions and all local codes or in their
absence in accordance with the latest edition of The National Fuel Gas Code (NFPA #54), the latest edition of the National
Electrical Code (NFPA#70) and the Occupational Safety and Health Act (OSHA) when applicable. Improper installation can create
a hazardous condition such as an explosion, fire, electrical shock or carbon monoxide poisoning resulting in property damage, per-
sonal injury or death.

Improper installation, adjustment, alterations, service or maintenance can cause injury, property damage or death. Refer to this
manual. For assistance or additional information consult a qualified installer, service agency or the equipment supplier.

Do not exceed the recommended input range of the SS2G. Under no circumstances shall the minimum draft adjustment be used
for the larger input range of this product. Improper adjustment may result in the dispersion of flue products (carbon monoxide)
into the building interior causing carbon monoxide poisoning or death.