Tjernlund PAI-1 & 2O Combustion Air In-Forcer 8504038 Rev A 05/01 User Manual

Page 10

Advertising
background image

9

NOTES: The IN-FORCER is always interlocked with the primary control of the appliance. Wire all other furnace/boiler controls as nor-
mally done when conventional venting before continuing. Disconnect power from the appliance before attempting to interlock IN-FORCER.

Step 1: Disconnect BLACK burner motor wire from the ORANGE wire on R8184G.
Step 2: Connect the BLACK burner motor wire to the YELLOW wire in IN-FORCER electrical box.
Step 3: Connect the ORANGE wire from R8184G to the BLACK wire in IN-FORCER electrical box.

Important: The ORANGE wire from R8184G should also be connected to the Ignition Transformer or Oil Valve.

Step 4: Connect the GREEN wire in IN-FORCER electrical box to the GREEN or ground wire of burner motor
Step 5: Connect the WHITE wire in IN-FORCER electrical box to the WHITE wire of R8184G.

NOTES: The IN-FORCER is always interlocked with the primary control of the appliance. Wire all other furnace/boiler controls as nor-
mally done when conventional venting before continuing. Disconnect power from the appliance before attempting to interlock IN-FORCER.
The instructions below assume that the IN-FORCER and SS1 are installed at the same time.

Step 1: Disconnect the BLACK burner motor wire from the ORANGE wire on R8184G.
Step 2: Connect the BLACK burner motor wire to the YELLOW wire in IN-FORCER electrical box.
Step 3: Connect the ORANGE wire on R8184G to terminal O in SS1 electrical box.

Important: The ORANGE wire from R8184G should also be connected to the Ignition Transformer or Oil Valve.

Step 4: Connect terminal Y on SS1 terminal strip to the BLACK wire in IN-FORCER electrical box.
Step 5: Connect the GREEN wire in IN-FORCER electrical box to the GREEN or ground wire of burner motor.
Step 6: Connect the WHITE wire in IN-FORCER electrical box to the WHITE wire of R8184G.

IN-FORCER MODELS PAI-1O & PAI-2O CONNECTED TO AN R8184G WITH THE APPLIANCE

(BURNER MOTOR LESS THAN 3 AMPS INDUCTIVE @ 120 VAC)

IN-FORCER MODELS PAI-1O & PAI-20 CONNECTED TO AN R8184G WITH TJERNLUND SS1 OR SS2 POWER VENTER

(BURNER MOTOR LESS THAN 3 AMPS INDUCTIVE @ 120 VAC)