Tjernlund PS1503 Duct Airstat Fan Proving Switch Rev  A 10/99 User Manual

Tjernlund products, inc, Model ps1503, Typical mounting locations & applications

Advertising
background image

MODEL PS1503

The Tjernlund Duct Airstat senses positive pressure in a forced
air heating and/or cooling system. The single pole, single throw,
snap-acting switch is activated by a diaphragm with integral
pressure probe inserted directly into the duct or plenum.

The Duct Airstat can be used to initiate such auxiliary devices
as: Duct Boosters, Electronic Air Cleaners, Electrical Duct
Heaters, and Humidifiers. The electrical contacts of the switch
are closed upon sensing positive air pressure generated by the
blower.

Switch actuates air
cleaner by sensing
positive plenum pressure.

Switch activates humidifier
by sensing positive plenum
pressure.

Switch proves operation
of blower by sampling
positive pressure.

ELECTRONIC AIR CLEANERS

HUMIDIFIERS

FAN OPERATION

Switch activates Duct Booster by sensing positive pressure on either plenum, trunk, or branch lines as shown in Figures A and B above.

TYPICAL MOUNTING LOCATIONS & APPLICATIONS

A

B

Trunk Line

Plenum

115-120V

Duct

Airstat

Duct

Booster

Electronic

Air Cleaner

Electronic

Duct Heater

Humidifier

Duct Booster

Branch

Run

WIRING:

All wiring must agree with applicable electrical codes
and ordinances. Typical diagrams are shown below.

SWITCH MUST BE

MOUNTED WITH

DIAPHRAGM IN

VERTICAL POSITION

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com

SIDE VIEW

TOP VIEW

LOCATION AND MOUNTING:

1. The duct Airstat must be mounted in a vertical position.
2. Drill a 11/32” hole in the duct or plenum to permit the inser-

tion the pressure probe. If furnace has central air-condi-
tioning, care must be taken so as not to drill into the cooling
coil when mounting the Duct Airstat on the furnace plenum.

3. Insert the pressure probe into the drilled hole, position the

Duct Airstat and mark the mounting holes. If necessary,
bend the mounting feet with pliers to match the contour of
the duct or plenum.

4. Remove control and drill or punch two 1/8” holes for

mounting screws.

5. Using the two sheet metal screws furnished, fasten the Duct

Airstat to the duct or plenum. Sealing gasket must be
mounted on pressure probe to ensure minimal air leakage.

OWNERS

INSTRUCTIONS

DO NOT DESTROY

DUCT AIRSTAT INCLUDES:

1. A fixed “fan-on” setpoint
(+ .05 + .02” W.C.)
2. Integral pressure probe
3. Sealing gasket
4. Mounting hardware

INSTALLATION:
CAUTION

1. Disconnect power supply before making wiring

connections to prevent electrical shock and
equipment damage.

2. All wiring must comply with applicable codes and

ordinances.

3. Always conduct a thorough checkout when installa-

tion is complete.

SEALING
GASKET

PRESSURE
PROBE