Fsad-12 wiring, Fsad-8/10 wiring, Internal factory wiring of fsad-12 – Tjernlund Auto-Draft FSAD & VSAD Series Inducers 8504090 Rev 11/00 User Manual

Page 10: Internal factory wiring of fsad-8/10

Advertising
background image

9

IMPORTANT: CONFIRM PROPER IMPELLER ROTATION (VSAD-SERIES ONLY)

All Auto-Draft® VSAD-Series Venters must use a Variable Frequency Drive (VFD) supplied by Tjernlund which is factory programmed specifi-
cally for the VSAD model being installed. IMPORTANT: Impeller must rotate counter-clockwise as viewed through Auto-Draft® discharge grille.
Auto-Draft® may appear to be operating properly but if it is only able to produce marginal draft the impeller may be rotating backwards.
Excessive amp draw from the motor may be a sign that the impeller is rotating backwards. Inspect impeller for proper rotation and follow amp
draw procedure below.

1. Depress DSPL key on the VFD until “IOUT” is lit.

2. Adjust speed adjustment knob on VFD clockwise to maximum Venter speed. VFD may trip out on overload (

oLI) shown in drive

display. Amp draw at maximum speed should not exceed amp ratings in “Specifications” on page 1.

3. While running at full speed, if amp draw is excessive or VFD trips out on overload (

oLI), disrupt power to the VFD and switch any

two leads to the M1, M2 or M3 terminal. Reestablish power to the VFD and repeat steps 1 and 2 and confirm proper rotation of
impeller and proper amp draw at maximum Venter speed.

ORANGE

BLUE

GREEN

RED

RED

FSAD-12 WIRING

COOLING FAN

MOTOR

GND

VERTICAL

TILT SWITCH

MOTOR

LIMIT

HIGH

LIMIT

L2

L1

GRAY

BLK

BLK

BLK

BLK

BLUE

BLUE

WHT/BRN

HORIZONTAL

TILT SWITCH

*

*

For vertical termination of the Auto-Draft , connect to orange wire and cap off gray wire as shown.
For horizontal termination of the Auto-Draft , connect to gray wire and cap off orange wire.

*

*

R

R

B

C

D

A = COOLING FAN POWER, 208-240VAC/60HZ/0.13 AMPS

B = SAFETY/PROTECTION CIRCUIT THROUGH TILT SWITCHES, 10VA MAX LOAD

C = GROUND CIRCUIT

D = MOTOR POWER - SWITCHED LOAD WITH APPLIANCE CALL, 208-240VAC/60HZ

BLACK

BLACK

THERMOSTAT

FAN

P/N 1303943 10/20/00

BLK

A

INTERNAL FACTORY WIRING OF FSAD-12

BLACK

BLACK

ORANGE

BLUE

GREEN

L2 = WHITE

L1 = RED

FSAD-8/10 WIRING

COOLING FAN

MOTOR

THERMOSTAT

FAN

GND

VERTICAL

TILT SWITCH

P/N 1303942 10/20/00

MOTOR

LIMIT

HIGH

LIMIT

L2

L1

GRAY

BLK

BLK

BLUE

BLUE

WHT/BRN

HORIZONTAL

TILT SWITCH

*

*

For vertical termination of the Auto-Draft , connect to orange wire and cap off gray wire as shown.
For horizontal termination of the Auto-Draft , connect to gray wire and cap off orange wire.

*

*

R

R

BLK

A

B

C

D

A = COOLING FAN POWER, 110-120VAC/60HZ/0.25 AMPS

B = SAFETY/PROTECTION CIRCUIT THROUGH TILT SWITCHES, 10VA MAX LOAD

C = GROUND CIRCUIT

D = MOTOR POWER - SWITCHED LOAD WITH APPLIANCE CALL, 110-120VAC/60HZ

INTERNAL FACTORY WIRING OF FSAD-8/10