General wiring – Chromalox CCAS-12 User Manual

Page 3

Advertising
background image

Draft Barrier Heater Installation (Wall)
1.
Once the correct mounting height is established, scribe or snap

a level line on the wall to maintain each heater back plate in
horizontal alignment, when mounting.

2. Remove heater front cover by lifting top rear edge to unsnap

cover from back plate (store cover in safe location to avoid
damage to the finish). (See Figure 2.)

3. Remove all appropriate knockouts from terminal boxes, partic-

ularly terminal box end knockouts when installing continuous
run heating. (See Figure 3.)

4. Mount the back panel to the wall using suitable fasteners (not

supplied). Should the wall surface be uneven, secure the heater
backplate to the high spots only to avoid a distorted appearance.

Draft Barrier Heater Installation (Floor)
1.
Unpack the heater and pedestal(s) from the carton (The

pedestals are packed at the end of carton) and lift the front/top
panels up and off the heater.

2. Disassemble the pedestal base from the pedestal pad.
3. Remove the desired terminal box cover(s) and supply wire

entry knockouts from the terminal boxes.

4. Secure a pedestal to each end of the heater bottom with #8

screws provided aligning the back and front edges of the pad
with the heater. This will align the supply entry knockout with
opening in pedestal pad.
TIP: Units longer than 4 feet will be provided with 3 or more
pedestals. The extra pedestals should be used to support the
middle of heaters.

5. Place heater on the pedestal base(s) and tighten all screws.

TIP: The height of the heater can be adjusted on the pedestal to
aid in leveling the heater by loosening the securing bolt at the
side of the pedestals.

6. Remove the terminal box cover and proceed to wiring instructions.

GENERAL

WIRING

Length

1-1/2

2

Back View

Bottom View

(Front Inlet Version Shown)

2-3/4

Terminal Box

Terminal Box

12

1

1

5-3/4

CAF-12

Side View

(Less End Cap)

Side View

(Less End Cap)

CCAS-12

5-3/4

1

1

12

Ground Continuity —

Note: All wiring should be done in accordance with local codes
and the National Electrical Code by a qualified person.

WARNING: Hazard of Electric Shock. Any installa-
tion involving electric heaters must be effectively
grounded in accordance with the National
Electrical Code to eliminate shock hazard.

Prior To Installation —

WARNING: Hazard of Electric Shock. Disconnect all
power before installing heater.

1. All branch circuit and service supply wiring must be complet-

ed to the heater terminal box location.

2. Check heater nameplate ratings to be sure heater voltage is

same as service supply.

3. Service supply entry is usually made to one heater terminal box

(see Figure 3) with through wiring (Factory Installed) being
used for interconnection of all heaters in a continuous run
installation.

Note: When heaters are mounted end to end, remove the finishing
end plate, install a chase nipple and locknut in the terminal box
end knockout to ensure grounding continuity and to protect the
wiring.

Where heaters are spaced apart, remove the finishing end plate,
and use rigid conduit (Provided by customer) for through wiring
and ground continuity. Do not exceed the allowable number of
conductors allowed by the National Electrical Code.

Note: See Table 3 for recommended service supply wire sizes.

4. Knockouts are provided at the back, bottom and ends of all
heater backs (see Figure 3). Terminal boxes are located at both
ends of every heater.

Table 3: Service Supply Wiring Sizes
Recommended minimum supply wire sizes are listed in the table
below:

Figure 3

Figure 2

Figure 4

Maximum Watts Per Circuit Using 75 Degree C. Wire

Rough In
Wire Size

120V

208V

240V

277V

347V

480V

600V

14

1440

2496

2880

3324

4164

5760

7200

Copper

12

1920

3328

3840

4432

5552

7680

9600

Wire

10

2880

4992

5760

6648

8328

11520

14400