Ordering information optional accessories, Specifications – Charles Bentley & Son AA Series User Manual

Page 2

Advertising
background image

Ordering Information

Optional Accessories

• Remote summary relay
• Battery

temperature

compensation

• Low DC voltage alarm relay
• High DC voltage alarm relay
• Current failure relay

• Combined Low/High voltage

alarm relays

• AC power failure relay

Specifications

AC Input

108-132 volts/60 Hz (220 volts/50 Hz optional)

Operating Temperature

0º to 50º C (32º to 122º F)

Storage Temperature

-20º to 60º C (-4º to 140º F)

Cooling

Convection

DC Output

- Float

2.16 VPC for lead Acid, 1.45 VPC for nickel cadmium

- Equalize

2.33 VPC for lead Acid, 1.55 VPC for nickel cadmium

Current Limit

Approximately 135%

Enclosure

304 stainless steel hinged cover to facilitate installation

12 Volt

Model

Number

Height
Inches

Width

Inches

Depth

Inches

Approx.

Weight

D.C. Output

Amps

System
Voltage

24 Volt

32 Volt

AA1206*

6

12

11

9

8.5

12

AA1210*

10

12

11

9

8.5

14

AA1220*

20

12

11

9

8.5

22

AA2406*

6

24

11

9

8.5

14

AA2410*

10

24

11

9

8.5

22

AA2420*

20

24

13

16.5

8.5

38

AA3206

6

32

11

9

8.5

22

AA3210

10

32

11

9

8.5

26

0

10

20 30

40

50

60

70

80

90 100

% OF RATED CHARGING CURRENT (AMPS)

VPC

2.5

2.4

2.3

2.2

2.1

2.0

1.9

1.8

Equalize

Float

Typical Output Curve

*UL Listed

Contact your Charles sales representative for specific
product information.

When ordering, please specify:

1. Model number
2. AC input: voltage & frequency
3. Battery type and number of cells
4. Ampere-hour capacity of battery
5. Recharge time desired
6. Description of load
7. Options

Charles Industries, Ltd.
Industrial Group
5600 Apollo Drive
Rolling Meadows, IL 60008 USA

Voice: (847) 806-6300
Fax: (847) 806-6352
E-mail: [email protected]

D-IND001-B01 Rev.

3

IS0 9000

REGISTERED

QUALITY SYSTEM

Advertising