evaporator unit (including liquid line connection, solenoid valve, expansion
valve, and suction line connection), returning to insulated suction line, suction
valve and then back to condensing unit.

2) If the condensing unit is located below the evaporator unit, use inverted U

trap to prevent liquid from flooding back to the compressor; if the elevation
difference is more than 10 ft or the line set exceeds 75 ft, use both inverted U
trap and suction accumulator.

3) If the condensing unit is located more than 10 ft above the evaporator unit,

use U trap to aid oil returning to the compressor.

4) Complete pipe brazing, check solenoid valve and expansion valve restrictions

and test leak.

5) Hook up the drain line and check if water drains.
The line sizes and refrigerant charges are listed as follows.

Model No

Equivalent

Line Set

Liquid

Line

Suction

Line

Drain Line

Recommended

Charge

WM-2500SSHWC

<= 75 FT

1/4" OD

3/8” OD

7/8” OD

R134a/19 OZ

WM-4500SSHWC

<= 75 FT

1/4" OD

1/2” OD

7/8” OD

R134a/26 OZ

WM-6500SSHWC

<= 75 FT

1/4" OD

1/2” OD

7/8” OD

R134a/32 OZ

WM-8500SSHWC

<= 75 FT

3/8" OD

5/8” OD

7/8” OD

R134a/40 OZ


7. Water Piping

f a water pump is used, install it before the water inlet so that the condenser
cooling water is fed from the discharge side of the pump.

Model No

Condensing Unit

Water Flow

(75°F inlet, gal/min)

Water-in

Connection

Water-out

Connection

Water Pressure

Drop (PSI)

WM-2500SSHWC

WM-250SCU-WC

0.2

3/8” FPT

1/2" ODF SOLDER

0.2

WM-4500SSHWC

WM-450SCU-WC

0.4

3/8” FPT

1/2" ODF SOLDER

0.2

WM-6500SSHWC

WM-650SCU-WC

0.6

3/8” FPT

1/2" ODF SOLDER

0.2

WM-8500SSHWC

WM-850SCU-WC

0.8

3/8” FPT

1/2" ODF SOLDER

0.4


8. Connecting Electrical Wires

Connect all electrical components using the wiring diagrams in accordance with
all state and local codes.

9. Evacuating, Charging and Starting the system

CAUTION:
Always use the superheat and subcooling, pressure readings to charge

refrigerant properly; the listed charge amounts are used for reference
only.


1) Evacuate the system; both discharge and suction valves must be in the

middle positions during evacuating.