Carrier 50EY User Manual

Page 5

Advertising
background image

NOTES:
1. Weights include economizer (Std)

2.

Center of gravity.

3. Do not locate adjacent units with discharge facing economizer inlet. Mini-

mum clearances to be:

Adjacent Units: 15

Ј

-0

Љ

Top of Units: No overhang
Condenser Coil: 4

Ј

-0

Љ

Economizer Side: 6

Ј

-0

Љ

Filter Access Side: 10

Ј

-0

Љ

(for removal of evaporator coil)

4. For smaller service and operational clearances, contact Carrier Applica-

tion Engineering department.

5. Bottom ducts designed to be attached to accessory roof curb. If unit is

mounted on dunnage, it is recommended the ducts be supported by cross
braces as done on accessory roof curb.

6. Dimensions are in inches. Dimensions in [

] are in millimeters.

7. For units with electric heat, a field-supplied 90° elbow must be installed

in the supply ductwork below the unit discharge.

UNIT SIZE

50E

OPERATING

WEIGHT

(lb)

A

B

CORNER WEIGHT

(lb)

ft-in.

ft-in.

1

2

3

4

J038

4282

7-7

5

16

3-10

1

2

961

858

1162

1302

J/K044

4508

7-3

13

16

3-11

1

2

973

868 1258 1409

J048

4795

7-2

3

16

3-10

3

32

1007

915

1368

1505

Fig. 4 — Base Unit Dimensions, 50EJ038-048 and 50EK044

LEGEND

VFD — Variable Frequency Drive

5

Advertising