OPERATING AND PROGRAMMING INSTRUCTIONS

8-3

Please note that the power supply is double rectified, so if 24VDC and 0VDC are switched

the controller will still work without problems. The power supply monitoring (see chapter 6.5.4)
will not work if 24VDC is connected to pin 2 and 0VDC is connected to pin 1.

J9: Inputs 9 to 16
Pin 1:

Input 9

Pin 2:

Input 10

Pin 3:

Input 11

Pin 4:

Input 12

Pin 5:

Input 13

Pin 6:

Input 14

Pin 7:

Input 15

Pin 8:

Input 16

Pin 9:

Common for inputs 9 until 16 (0VDC or 24VAC neutral)


J10: Relay outputs 1 to 8
Pin 1:

Common for output 1

Pin 2:

Output 1

Pin 3:

Output 2

Pin 4:

Output 3

Pin 5:

Output 4

Pin 6:

Common for output 2, 3, 4, 7 and 8

Pin 7:

Output 5

Pin 8:

Common for output 5 and 6

Pin 9:

Output 6

Pin 10:

Output 7

Pin 11:

Output 8, normally open contact

Pin 12:

Output 8, normally closed contact


J11: Analogue I/O and digital output
Pin 1:

NTC sensor 1, wire 1

Pin 2:

NTC sensor 1, wire 2

Pin 3:

NTC sensor 2, wire 1

Pin 4:

NTC sensor 2, wire 2

Pin 5:

Analogue out, ground

Pin 6:

Analogue out, 0-10VDC

Pin 7:

GND

Pin 8:

+24VDC

Pin 9:

Digital output 24VDC, not potential free, max. 20mA