SUPPLEMENT – VENTING INSTRUCTIONS FOR INSTALLATION AND OPERATING INSTRUCTION MANUALS  

238‐48384‐00, 238‐44727‐00, 238‐44445‐00, 238‐48144‐00, 238‐47936‐00, 238‐45917‐00, 238‐45637‐00, 

238‐47448‐00, 238‐48071‐00, 238‐49060‐00, AND 238‐47707‐00 FOR HIGH EFFICIENCY CONDENSING 

COMMERCIAL, POWER DIRECT VENT COMMERCIAL, POWER VENT COMMERCIAL, RESIDENTIAL POWER 

DIRECT VENT, and RESIDENTIAL POWER VENT MODEL SERIES 

INSTALLATION OF CENTROTHERM INNOFLUE® SINGLE WALL POLYPROPYLENE VENTING SYSTEMS 

This supplement is for the installation of polypropylene single wall venting system manufactured by Centrotherm ECO 
Systems, LLC.  The Centrotherm venting system is a CSA approved alternative to the PVC, ABS, and CPVC venting 
components for the High Efficiency Commercial Condensing, Power Direct Vent Commercial, Power Direct Vent 
Residential, and Residential Power Vent model series.   
 
The Centrotherm venting system components are ULC S636 approved and listed by a recognized agency and may be 
installed in the U.S. and Canada.  All components used must be from the same manufacturer and are designed for use 
with the above noted products.  The Centrotherm components may be purchased from plumbing supply distributors.  
The vent size diameter and maximum vent lengths must be followed as detailed in the Installation and Operating 
Instruction Manual that was supplied with the water heater.  Thoroughly read and understand the venting section of the 
instruction manual supplied with the water heater before proceeding with the following instructions in this supplement.  
The vent terminals supplied with the water heater or the factory approved accessory vent terminal kits must be used 
with this venting system. 
 

WARNING

The venting system must be properly installed. Failure to properly install the vent system could result in property
damage, personal injury, or death.

DO NOT install damaged venting system components. If damage is evident then please contact the supplier where
the water heater or venting system components were purchased for replacement parts.

Use only the vent terminals provided or factory authorized terminals for venting this water heater.

The water heater requires its own separate venting system. Do not connect the exhaust vent into an existing vent pipe
or chimney.

All of the exhaust venting connections must be leak checked with a soap solution upon initial start-up of the water
heater. Any leaks must be repaired before continuing operation of the water heater.

Do not terminate the venting where noise from the exhaust or intake will be objectionable. This includes locations
close to or across from windows and doors. Avoid anchoring the vent and intake pipes directly to framed walls, floors,
or ceilings unless rubber isolation pipe hangers are used. This prevents any vibrations from being transmitted into the
living spaces.
Do not exceed the venting distances or the number of elbows listed in the instruction manual supplied with the water
heater. Exceeding the maximum venting distances may cause the water heater to malfunction or cause an unsafe
condition.

DO NOT operate this water heater until the venting installation is complete and the piping completed. Failure to
complete installation before operation can result in property damage, personal injury, or death.

DO NOT install Centrotherm Innoflue venting components with any other manufacturer’s vent components.
Centrotherm Innoflue components must be used exclusively throughout the entire venting system from the water
heater coupling or vent connection to the outside wall or ceiling near the vent terminal location.
This supplement is intended only for additional information for installing Centrotherm Innoflue single wall venting
system and the instruction manual supplied with the water heater must be followed for the detailed information
provided for the venting system installation.

 