Bradford White TW4-75S-76B-3X User Manual

Page 8

Advertising
background image

8

Minimum Clearances

This installation must allow access to the front of the water heater and
adequate clearance must be provided for servicing and operating this water
heater. The water heater may be installed on either a combustible or non-
combustible floor. If the water heater is to be installed directly on carpeting, it
must be installed on top of a metal or wood panel extending beyond the full
width and depth of the appliance by at least three (3) inches (7.6 cm) in any
direction or, if the appliance is to be installed in an alcove or closet, the entire
floor must be covered by the panel. The minimum clearances to combustibles
for this water heater are: zero (0) inch (0 cm) from the sides and rear, five (5)
inches (12.7 cm) from the front of the jacket, zero (0) inch (0 cm) from the vent
connector and fifteen (15) inches (38.1 cm) from the jacket top.

Venting

This venting section is divided into two parts. Part I will cover venting
specifications for 48 Gal (181.6 L
), 65 Gal (246.0 L), and 75 Gal (283.9 L)
models. Part II will cover venting specifications for 40 Gal (151.4 L
) and
50 gal (189.2 L
) models. Refer to the rating plate located on the water
heater for correct model identification.

Figure 1 - Vent Terminal Clearances

WARNING

Failure to adhere to these installation and operating instructions may
create a hazard to life and property and will nullify the warranty.

Advertising
This manual is related to the following products: