62

Code

Code Description

Remedy

14

Thermal Fuse

Check gas type of unit and ensure it matches gas type being used.
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-cycling.
Ensure dip switches are set to the proper position.
Check for foreign materials in combustion chamber and/or exhaust piping.
Check heat exchanger for cracks and/or separations.
Check heat exchanger surface for hot spots which indicate blockage due to scale build-
up. Refer to instructions in manual for flushing heat exchanger.
Measure resistance of safety circuit.
Ensure high fire and low fire manifold pressure is correct.
Check for improper conversion of product.

16

Over Temperature
Warning

Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-cycling.
Check for foreign materials in combustion chamber and/or exhaust piping.
Check for clogged heat exchanger.

25

Condensate Trap
Error

Condensate container is full.
Check condensate drain for blockage.
Replace condensate trap.

31

Burner Sensor Error

Measure resistance of sensor.
Replace sensor.

32

Outgoing Water
Temperature Sensor
Fault

Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.

33

Heat Exchanger
Outgoing Temperature
Sensor Fault

Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.

52

Modulating Solenoid
Valve Signal Abnormal

Check modulating gas solenoid valve wiring harness for loose or damaged terminals.
Measure resistance of valve coil.

61

Combustion Fan
Failure

Ensure fan will turn freely.
Check wiring harness to motor for damaged and/or loose connections.
Measure resistance of motor winding.

65

Water Flow Control
Fault

The water flow control valve has failed to close during the bath fill function. Immediately
turn off the water and discontinue the bath fill function. Contact a state qualified or
licensed contractor to service the water heater.

71

SV0, SV1, SV2, and
SV3 Solenoid Valve
Circuit Fault

Replace the PC board.

72

Flame Sensing Device
Fault

Ensure flame rod is touching flame when unit fires.
Check all wiring to flame rod for damage.
Remove flame rod and check for carbon build-up; clean with sand paper.
Check inside burner chamber for any foreign material blocking flame at flame rod.
Measure micro amp output of sensor circuit with flame present.
Replace flame rod.

73

Burner Sensor Circuit
Error

Check sensor wiring and PC board for damage.
Replace sensor.

LC

Scale Build-up in Heat
Exchanger (when
checking maintenance
code history, “00” is
substituted for “LC”)

Flush heat exchanger. Refer to instructions in manual.
Replace heat exchanger.
NOTE: The LC code is the only error code that will allow the unit to keep running. The
display will alternate between the LC code and the temperature setting. The controller
will continue to beep. The LC code will reset if power is turned off and then on.