*Field-supplied.

NOTES:
1. Factory wiring is in accordance with NEC; field modifications or addi-

tions must be in compliance with all applicable codes.

2. Wiring for field power supply must be rated 75 C minimum. Use cop-

per, copper-clad aluminum, or aluminum conductors. Maximum
incoming wire size for each terminal block is 500 kcmil.

3. Terminal blocks TB3 and TB4 are for external field control connec-

tions. Control connections are to be Class 1 wiring.

4. Field-supplied components (IFC, LLS-A, and LLS-B) must have a maxi-

mum sealed coil rating of 30 va each (.25 amp at 120 vac, .13 amp at
230 vac). AHMS IFC-AUX must have a minimum pilot duty rating of
200 va (1.7 amps at 120 vac, 0.9 amps at 230 vac) each.

5. Replacement of factory wires must be with type 105 C wire or its

equivalent.

6. Field-supplied liquid line solenoid valves installed at the evaporator are

required on all units.

7. Units have 175 va of power available for field-installed accessories.

Fig. 24 — Field Wiring, Single ModuPanel™ Control, 38AH044-084 Dual-Circuit Units

LEGEND

AHMS — Air Handler Motor

Starter

AUX

Auxiliary

C

Compressor Contactor

FU

Fuse

GND

Equipment Ground

IFC

Indoor Fan Control

kcmil

Thousand Circular Mils

LLS

Liquid Line Solenoid

NEC

National Electrical Code

(U.S.A. Standard)

SDR

Solenoid Drop Relay

TB

Terminal Block

TBX

Terminal Block for Variable

Air Volume Units

TM

Timer Motor

TR

Timer Relay

TRAN — Transformer
U

Unloader Solenoid

Factory Wiring
Field Wiring