LOW SIDE PORT

(SUCTION)

COMP.

HIGH SIDE PORT

(DISCHARGE)

RED HANDLE

(HIGH SIDE)

RED HOSE

(HIGH SIDE)

REFRIGERANT CONTROL VALVE

(YELLOW HANDLE)

BLUE HOSE
(LOW SIDE)

FILTERED HOSE

CONNECTOR

3 PLACES

REF.

VAC.

PUMP

YELLOW HOSE

BLUE HANDLE

(LOW SIDE)

VACUUM

VAPOR CHARGE

LIQUID HI SIDE

LOW SIDE

LIQUID CHARGE

NOTE:
*Connection should be made to service valve or access fitting.

GAUGE RECALIBRATION:

Remove lens cover. Turn recalibrator

screw in the opposite direction to

desired movement of pointer until

gauge reads “0”. Replace lens.

No more than 1/2 Turn.

*

*

Patented Metering

Device Engaged-

Converts Liquid to Vapor

OBSERVE OPERATING PRESSURE:

1. Close red “HI” and blue “LO” side valves,

finger tight.

2. Connect blue low side hose to system’s

low side service port and the red high side

hose to the system’s high side service port.

3. Once the hoses have been connected, the

system pressure will be displayed on the gauge

face.

NOTE: A system that has service valves; the

valves should be cracked open after

connection. Hoses must be purged.

RECOVERING REFRIGERANT:

1. Turn yellow “REF” valve fully counter-clockwise,

finger tight, to the “VACUUM, VAPOR, LIQUID

HI SIDE” position.

2. Close the blue “LO” side valve and red “HI”

side valves, finger tight.

3 Connect blue low side hose to system’s low side

service port. Connect red high side hose to the

system’s high side service port.

4. Follow the instructions provided with the

recovery unit for proper recovery of refrigerant

from the system.

NOTE: Typically, the yellow hose is

connected to the inlet of the recovery unit.

EVACUATE (VACUUM):

1. Remove all refrigerant from system using a

refrigerant recovery system.

2. Turn yellow “REF” valve fully counter-clockwise,

finger tight, to the “VACUUM, VAPOR, LIQUID

HI SIDE” position.

3. Connect blue low side hose to system’s low

side service port. Connect red high side

hose to the system’s high side service port.

4. Connect the center hose (yellow) to the

vacuum pump.

5. Open red “HI” and blue “LO” side valves.

6. Start vacuum pump.

7. Evacuate system according to manufacturers

specifications then close red “HI” side and blue

“LO” side valves and turn off vacuum pump.

CHARGING:

1. Disconnect the yellow hose from vacuum pump

and connect to refrigerant tank.

2. Slightly open the refrigerant supply valve on the

tank. Purge air from the yellow hose at the

manifold by loosening the yellow hose fitting

connection. When complete, tighten hose

connection and turn off refrigerant supply valve.

3 System can now be charged according to

the manufacturers specification.

CHARGING OPTIONS:
Liquid High Side Charging:
To draw liquid from

tank and charge into system high side. Turn the

yellow “REF” valve fully counter-clockwise to the

“VACUUM, VAPOR, LIQUID HI SIDE” position - finger

tight. Close the blue “LO” side valve - finger tight.

continued on back page

It is unlawful to discharge or exhaust refrigerants into the atmosphere. Imperial strongly

recommends using recovery or recycling equipment for proper disposal of refrigerants.