PNOZ s7.2

Operating Manual PNOZ s7.2
21866-EN-08

6

Expansion options

Please note the max. power consumption of the

contact expansion modules (see technical data

PNOZ s7.1).

: Contact expansion module PNOZ s7.1 with ter-

minator

: Contact expansion module PNOZ s7.2

: Expansion module PNOZ s7, s8, s9, s10, s11

as a terminator

: Base unit

: Contact expansion module PNOZ s7.1

: Contact expansion module PNOZ s7.2

: Contact expansion module PNOZ s7.1

: Contact expansion module PNOZ s7.2

: Contact expansion module PNOZ s7.2 with ter-

minator

Wiring

Please note:

}

Information given in the "Technical details" must be followed.

}

Outputs 13-14, 23-24, 33-34, 43-44 are safety contacts; outputs 51 -52 are auxiliary

contacts (e.g. for display).

}

Auxiliary contact 51-52 should

not be used for safety circuits!

}

To prevent contact welding, a fuse should be connected before the output contacts (see

technical details).

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in-

ductive loads.