Vertical sidewall installation, Vertical sidewall application, How to use the vent graph – Vermont Casting DVRSR User Manual

Page 12

Advertising
background image

- 12 -

Fig. 19

COMBUSTIBLE WALLS (Fig. 19): Cut a 9-3/8"H x 9-3/8"W (240
mm x 240 mm) hole through the exterior wall and frame as shown

NON-COMBUSTIBLE WALLS (Fig. 19): Hole opening must be

7.5" (190 mm) in diameter.

(240mm)

9-

3/8

"

9-

3/8

"

(240mm)

7-

1/2

"

(190mm)

Vent Opening —
Combustible Wall

Vent Opening —
Noncombustible Wall

(framing detail)

STEP 1

Locate vent opening on the wall. It may be necessary to first
position the fireplace and measure to obtain hole location.
Depending on whether the wall is combustible or non-
combustible, cut opening to size. Fig. 19.
(For combustible walls first frame in opening).

VERTICAL SIDEWALL INSTALLATION

STEP 2

Fiig. 20. Measure wall thickness and cut adjustable zero
clearance sleeve parts to proper length (MAXIMUM 12"/
305mm). Adjust sleeve to minimum (9-3/8" x 9-3/8") and
attach to firestop with #8 sheet metal screws (supplied).
Install firestop assembly.

Zero clearance sleeve is only required for
combustible walls.

VERTICAL SIDEWALL APPLICATION

SEE PAGE 14 FOR VENTING

REQUIREMENTS FOR SNORKELS.

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

eg: A

eg: B

VERTICAL DIMENSION FROM THE FLOOR OF THE UNIT

TO THE CENTRE OF THE HORIZONTAL VENT PIPE

Fig. 18

HOW TO USE THE VENT GRAPH

1.

Determine the height of the centre of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph (Fig. 18),
locate the point it intersects with the slanted graph
line.

2.

From the point of this intersection, draw a vertical
line to the bottom of the graph.

3.

Select the indicated dimension, and position the
fireplace in accordance with same.

EXAMPLE

A:

If the vertical dimension from the floor of the unit is 11
feet (3352mm) the horizontal run to the face of the outer
wall must not exceed 14 feet (4267mm).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7 feet
(2133mm), the horizontal run to the face of the outer wall
must not exceed 8-1/2 feet (2590mm).

VERTICAL SIDEWALL VENTING GRAPH

(Dimensions in Feet)